Use plastic cable glands/conduit couplings with
multiple cable grommet. These can be detached
with the plug-in connection terminals.
Do not supply voltage to the outputs.
A short-circuit on the outputs causes one of the
replaceable fuses to trip.
Do not set the remote reset so that it operates
(automatically) in cycles.
Wire the safety circuit inputs via contacts (relay
contacts) only.
The limiters in the safety interlock (e.g. safety
temperature limiter, emergency stop) must iso-
late terminal35, as well as the optional safety-
relevant inputs, e.g. at terminals 36 to 41, if these
are parameterized, from the voltage supply. If the
safety interlock is interrupted, the display shows
a blinking
51
as a warning signal and all of the
BCU’s gas valve outputs are disconnected from
the electrical power supply.
Connected control elements must be equipped
with protective circuits in accordance with the
manufacturer’s instructions. The protective circuit
prevents high voltage peaks which can cause
malfunctioning of the BCU.
Install the ignition cable in the BCU in the desig-
nated cable duct1 and feed it out of the BCU on
the shortest possible route via the cable gland.
2
1
Observe the maximum duty cycle for the ignition
transformer (see manufacturer’s instructions).
Adjust the minimum pause timet
BP
(param-
eterA062) correspondingly, if required.
All functions of the inputs at terminals 1 to 7
and 35to41, as well as of contacts 80to82,
85to87, 90to92 and 95to97, depend on
parameters I050toI074.
1 Disconnect the system from the electrical power
supply.
Before wiring, ensure that the yellow parameter
chip card has been inserted in the BCU.
Screw terminals or spring force terminals are
available for the BCU:
Screw terminals, Order No. 74924876,
spring force terminals, Order No. 74924877.
3 Wire as shown on the connection diagram, see
from page7 (Connection diagram).
4 After wiring, close the housing cover again and
tighten the cover screws to 2.4Nm.