6 EA16
6. TROUBLE SHOOTING
SYMPTOM CAUSE CORRECTION
Residual voltage below 5VAC Reference from 5. Field Flashing
F+, F polarity reversed F+ and F reverse the connection
F+, F, P1, P2, VS1, VS2 not
connected
Reference from Figure 3 and 4 connection
Burnt fuse Change fuse 16A 250V
Ext. Switch (Breaker) not turned on
Switch on (ON)
Voltage does not
build up
Engine RPM under speed Increase engine speed / frequency above25HZ
Poor adjustment is made Read start procedure carefully and adjust again
U/F protection activated Increase generator speed
Out voltage low
U/F activated / Incorrect voltage
selection
Read user’s manual to select correct voltage
Poor adjustment is made Read start procedure carefully and adjust again
Out voltage high
Incorrect voltage selection Read user’s manual to select correct voltage
Poor adjustment is made Read start procedure carefully and adjust again
Out voltage instable
Field voltage requirement lower
the rang of regulator
Inquire our distributor to solve
Use only original supplied spare protection fuse for fuse replacement.
Please accept our sincere apology if any modification in performance, specification or appearance is
made without prior notice.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kutai electronics EA16 and is the answer not in the manual?

Kutai electronics EA16 Specifications

General IconGeneral
BrandKutai electronics
ModelEA16
CategoryController
LanguageEnglish