Symptom Possible Cause Possible Solution
No discharge of air Cord is not plugged in Make sure cord is plugged in and try to turn the unit on pressing buttons
Power is not on on control panel and remote control. Check the circuit breaker or check
Circuit breaker/GFCI GFCI reset button.
Not cooling Water flow regulator at low setting Change the water regulator setting to MAX. Check the water level
and turn on the pump by pressing COOL button.
Low/No water Check Water
Odor emission Brand new unit Brand new media will initially have an odor which will dissipate within a
Old unit with algae week of initial use. If the unit is not new, there may be an algae issue
– replace the pad and maintain regularly.
Water droplets coming Calcium saturated water Drain water, deep clean and clean the media.
out of air outlet Clogged media Media may need to be replaced.
The unit will not respond Damaged PCB Try with remote control. If the unit responds, PCB board fasteners loose.
Moisture in PCB If neither control panel nor remote control command works, PCB board
Remote control batteries damaged - contact service technician.
Try using remote control to see if the unit responds. If the unit responds
briefly, likely cause is the moisture in the PCB. Turn off unit by unplugging
it from the power. Drain, clean and dry the unit, possibly replace the media.
Refill it with fresh water.
Check Batteries
Unit is making noise Calcium build up in blower Deep clean the unit -remove calcium debris. If the water level is near
Low or no water in the reservoir empty pump will make loud noise.
The unit will not Damaged PCB Try to use remote control to see if the unit responds
turn off Remote Control Batteries Check batteries