SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
Page 10 of 10
Address
Description, Units
Scale Factor
30009
Local Temperature Probe Reading, Degrees C
Note: A shorted probe will give a reading of 273 and an open
probe will give a reading of+273
None
30010
Temperature Probe Status
OK=0,SHORTED=1,OPEN=2,HARDWARE FAILURE=3
None
30011
Maximum Settable Alarm Voltage, MAXAV, Volts
0.1
30012
Maximum Settable Alarm Current, MAXAI, Amps
0.1
30013
Over Temperature Probe Reading, Degrees C
Note: A shorted probe will give a reading of 273 and an open
probe will give a reading of+273
None
30014
Over Temperature Probe Status
OK=0,SHORTED=1,OPEN=2,HARDWARE FAILURE=3
None
30015
Charger Series. (0=TPSD,1=A36D)
None
30016
Battery Voltage, Volts
Note: This point should only be monitored when DI 10015=1
NOT AVAILABLE= 30000, FAILED = 30001
0.1
30017
Aux Temperature Probe #1, C
Note: NOT AVAILABLE=30000, SHORTED=30001,
OPEN=30002, FAILED=30003
None
30018
Aux Temperature Probe #2, C
Note: NOT AVAILABLE=30000, SHORTED=30001,
OPEN=30002, FAILED=30003
None
30019
Low Voltage Alarm Status (0=NO ALARM,1=LOW VOLTAGE
ALARM,2=LOW BATTERY VOLTAGE ALARM)
None
30020
P60-407S Board Failure Alarm (0=N/A,1=NO ALARM,2-
ALARM)
None