FMS Commissioning
Function test Signal on terminal 2 = 0 Aids
Control quantity (load rating) is minimum.
Selector switch for mode (2) set to "Automatic”
Apply voltage to unit:
Unit performs a self-test
FMS appears briefly on display
Software version No. appears on display
Compare software version No. with number on the sticker
- operating display (5) lights up
- fuel LED (6 or 7) lights up
- the four "CLOSED” LEDs (B) light up A8
Selector switch (1) to "Status”
"OFF” appears on the display
Selector switch (1) to "Load rating”
The following appears:
- for external load default 200
- for internal load control unit 0
Set selector switch (1) to "Set-point feedback”
- the programmed value of the external feedback appears
(120, if no curve has yet been programmed)
Set selector switch (1) to "Actual value feedback”
- the instantaneous value of the external feedback appears
via 0 … 20 mA 0
via 4 … 20 mA 200
via potentiometer 120
(normally, but not necessarily)
_________________________________________________________
The values indicated only appear, however, if the control element is
situated at the bottom stop.
_________________________________________________________
Set selector switch (1) to "Load rating”
and
Press acceptance (3) (and keep pressed)
- The instantaneous value of the correction inputs is displayed
- KO appears between the channels
the display is in %, irrespective of the input signal setting
(0 … 20 mA or 4 … 20 mA)
»
»
»
»
»
LAMTECLAMTEC
xxx
xxx
xxx
xxx
5
B
6 7
1
ENTER
LAMTECLAMTEC
xxx
xxx
xxx
xxx
3
1
POWER OIL GAS
xxx
LOAD RATING
(CORR. INPUT)
LOAD RATING
(CORR. INPUT)
STATUS
(CORR. RANGE)
SETPOINT
FEEDBACK
ACTUAL VALUE
FEEDBACK