System Operation Messages / Faults
Fault code number Aids
H / Ü 321* Wire break feedback channel 1 E9
H / Ü 322* Wire break feedback channel 2 E9
H / Ü 323* Wire break feedback channel 3 E9
H / Ü 324* Wire break feedback channel 4 E9
H / Ü 325* Wire break feedback channel 5 E9
H / Ü 351* Barred curve change with burner running G3
put defective C4
Ü 372 Load value difference between HP and UE too great A7,D11
Ü 381 Difference between HP & UE too great
Correction input 1 A7,F6
Ü 382 Difference between HP & UE too great
Correction input 2 A7,F6
Ü 391 Fuel valves opened in ST operating mode A7,A19
H 392 Remote no longer responds (time-out)
H 393 Remote shut-off has been triggered
(shut-off via interface)
Ü 400 Different point number on acceptance A23
H / Ü 451* Ignition position was exited in ignition mode, channel 1 E18
H / Ü 452* Ignition position was exited in ignition mode, channel 2 E18
H / Ü 453* Ignition position was exited in ignition mode, channel 3 E18
H / Ü 454* Ignition position was exited in ignition mode, channel 4 E18
H / Ü 455* Ignition position was exited in ignition mode, channel 5 E18
H 500 Internal comparison: relay output terminal 67 does not pull on A19, A7
H 501 Internal comparison: relay output terminal 43 does not pull on A19, A7
H 502 Internal comparison: relay output terminal 16 does not pull on A19, A7
H 503 Internal comparison: relay output terminal 11 does not pull on A19, A7
H 504 Internal comparison: relay output terminal 45 does not pull on A19, A7
H 505 Internal comparison: relay output terminal 68 does not pull on A19, A7
H 506 Internal comparison: relay output terminal 36 does not pull on A19, A7
H 507 Internal comparison: relay output terminal 41 does not pull on A19, A7
H / Ü 352** Inadmissible curve selection (no selection signals present) G4
H / Ü 353** Inadmissible curve selection
(more than one selection signal present simultaneously) G4
H 360 Fault switch-off through integral O regulator
2
H / Ü 361 Different status from ignition position relay E6
H / Ü 370 Internal communication between processors defective A20
H 371 Internal load out
86