27
Seasonal energy performance ratio
Annual electricity consumption
Parameters at full load and reference ambient temperature at rating point A
Rated refrigeration capacity P
A
13,40 kW
Rated power input D
A
5,15 kW
Rated energy efficiency ratio EER
DC,A
2,59 [-]
Parameters at rating point B
Rated refrigeration capacity P
B
12,51 kW
Rated power input D
B
3,35 kW
Rated energy efficiency ratio EER
DC,B
3,72 [-]
Parameters at rating point C
Rated refrigeration capacity P
C
11,61 kW
Rated power input D
C
2,09 kW
Rated energy efficiency ratio EER
DC,C
5,53 [-]
Parameters at rating point D
Rated refrigeration capacity P
D
10,72 kW
Rated power input D
D
1,09 kW
Rated energy efficiency ratio EER
DC,D
9,78 [-]
Degradation co-efficient chillers C
dc
0,90 [-]
GWP of the refrigerant 2088
kg CO
2 eq
(100 years)
Contact details
LAUDA Ultracool S.L. - C/ Colom 606, 08228
Terrassa (Barcelona), Spain