EasyManuals Logo

LAUER PCS 091 User Manual

Default Icon
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
11
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
© Systeme Lauer GmbH Lauer-driver
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
○○○○○
○○
A1.5 Program integration
Regarding the integration into your program, the following transfer operations
must be executed (non-required functions can be skipped):
All values read by the PCS must be copied to the corresponding ABx.y. This
affects:
word 15 to word 19 (ABx.30 to ABx.39)
all used message bits
all variables
All values modified by the PCS must be written back into the corresponding
flags/flag bytes/flag words. This affects:
word 4 to word 14 (ABx.8 to ABx.29)
all message bits with erase behavior 2
all message bits for concealed logging with erase behaviors 2 -4
all preset values
After restart, the PCS proceeds with the following assumptions:
Date and time as well as the timer have become invalid and will therefore be
transferred immediately.
All message bits are in the same state as before switching off.
0 is selected as idle text.
All menus have been terminated before switching off, otherwise they must
be restarted.
After restart, the momentary pushbuttons and DIL switches will all be
transferred once.
This run-up behavior is to be noted when presetting the transfer area.