12
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
© Systeme Lauer GmbHLauer-driver
○○○○○
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
○○
Only the listing for slot 2 (9002 programming unit) is printed! The listing for slot 3
is identical with the slot 2 except for the EBx/ABx numbers (EB2.Y and AB2.Y are
replaced with EB3.Y and AB3.Y).
9002 PCS9002\FB200
NETWORK: 0001
NAME: HANT_PCS
BEZ: RESET (E/Ex/A/Ax/M/Mx/SM/SMx/T/Z/TN/B2/B8/B16/ANZ) (I/O) M
I
BEZ: ERROR (E/Ex/A/Ax/M/Mx/SM/SMx/T/Z/TN/B2/B8/B16/ANZ) (I/O) M O
BEZ: BAUD (E/Ex/A/Ax/M/Mx/SM/SMx/T/Z/TN/B2/B8/B16/ANZ) (I/O) MB I
BEZ: TOGGLM (E/Ex/A/Ax/M/Mx/SM/SMx/T/Z/TN/B2/B8/B16/ANZ) (I/O) M O
:***
NETWORK: 0002
:L =BAUD
:U KH 3
:= AB 2.1 BAUD RATE -> COMMAND BYTE
:U SM 2 ^ activating flag
:SPZ =NORM FIRST CYCLE?
:L AB 2.1
:O KH C0
:= AB 2.1 THEN RESET COMMAND -> COMMAND B.
:BA PB 201 AND MACHINE SPEC. PRESETTINGS
:SP =END
NORM :UN =TOGGLM
:= =TOGGLM
:SPZ =END SHORT CYCLE?, IF YES -> END
:L AB 2.1
:O KH 40
:= AB 2.1 LONG CYCLE -> COMMAND B.
:BA PB 200 COPIES ALL EB2.X -> AB2.X
:L AB 2.6
:O AB 2.7
:<> KH 0 FAULT FOUND?
:= =ERROR THEN SET FAULT BIT AND
:BAB PB 202 CALL EMERGENCY SETTINGS!
:U =ERROR
:U =RESET
:SPZ =END IF FAULT AND RESET, THEN
:BA PB 201 MACH. SPEC. PRESETTING AND COMM.START
END:***
A2.Program listing
A
Program listing