What to do if my LEGRAND UPS says overloaded?
- RRichard SmithAug 3, 2025
If the LCD on your LEGRAND UPS indicates “UPS is overloaded” or has already shut down, it's likely due to an overload. In Normal or Battery mode, shutdown times vary based on overload percentages: a 110% overload triggers an alarm for 20 seconds before shutdown, a 125% overload triggers an alarm for 10 seconds before shutdown, and a 150% overload causes an immediate shutdown. To resolve this, reduce the load, and then press the power button to re-establish power to the UPS outlets.