Wattstopper
®
Dual Technology Wall Switch Occupancy Sensors (version 3)
Interrupteur mural avec détecteurs de mouvement à technologie double (v3)
Sensores de ocupación e interruptor de pared con tecnología doble (v3)
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 24000 – 10/18 rev. 3
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: DW-100/DW-200
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
DESCRIPTION AND OPERATION
The DW Dual Technology Wall Switch sensors combine advanced passive infrared (PIR) and ultrasonic technologies into one unit. The
combined technologies help to eliminate false triggering even in difficult applications.
Selectable operating modes allow the sensor to turn a load ON, and hold it ON as long as either or both technologies detect occupancy.
After no movement is detected for the selected time delay, the lights switch OFF. A “walk-through” mode can turn lights off after only 3
minutes, if no activity is detected after 30 seconds following an occupancy detection.
The DW-100 has one relay and one ON/OFF button. The DW-200 contains two relays and two ON/OFF buttons to allow control of one
or two loads independently. Pressing a button toggles the state of the corresponding relay.
DW sensors contain a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light levels drop, even if the
area is occupied. In the DW-200, light level only affects the load on Relay 2. Users can overrule this function by pressing the ON/OFF
button. See Light Level Adjustment.
Turning ON the Load (ON Mode)
The relays are programmed independently for either Auto ON or Manual ON. In either mode, the load can be turned ON or OFF using
the ON/OFF button.
Manual ON
DIP 8 ON for Relay 1
DIP 9 ON for Relay 2
With an ON Mode DIP switch in the ON position, the occupant must press the ON/OFF button to turn
ON the load. The sensor keeps the load ON until no motion is detected for the selected time delay.
There is a 30 second re-trigger delay. If occupancy re-triggers during the delay (see Trigger Mode), the
sensor turns the load back ON. After the re-trigger delay elapses the ON/OFF button must be pressed to
turn ON the load.
Auto ON
DIP 8 OFF for Relay 1
DIP 9 OFF for Relay 2
With an ON Mode DIP switch in the OFF position, the load turns ON and OFF automatically based on
occupancy. If the load is turned OFF manually, Presentation Mode operation applies. This prevents
the load from turning ON automatically after it was deliberately turned OFF. Pressing the button to turn
lights ON returns the sensor to Auto ON mode.
Model # Relay Default ON Mode DIP Switch # Setting
DW-100 1 Manual ON 8 ON
DW-200 1
2
Auto ON
Manual ON
8
9
OFF
ON
SPECIFICATIONS
Voltages:
DW-100 & DW-200................................ 120/277VAC, 50/60Hz
Load Limits for each relay:
@120VAC .........................0-800W tungsten or ballast, 1/6 HP
@277VAC .......................................................0-1200W ballast
Load Type Compatibility:
Incandescent, fluorescent, magnetic or electronic ballast
Horsepower Rating (each relay) .................. 1/6 HP @120VAC
Time Delay Adjustment ............................................ 5 to 30 minutes
Walk-Through Mode ........... 3 minutes if no activity after 30 sec.
Test Mode .................. 5 sec. for 10 min. with DIP switch setting
PIR Adjustment ............................................ High or Low (DIP switch)
Ultrasonic Adjustment .................Minimum to Maximum (trimpot), Off
Frequency ..........................................................................40kHz
Light Level Adjustment ................................................. 8fc to 180+fc
Alerts ................................................................... Selectable Audible
US Patents: 5640113, 6617560
DW 100 DW-200
Question and Answer IconNeed help?

Do you have a question about the LEGRAND Wattstopper DW-100-B and is the answer not in the manual?

LEGRAND Wattstopper DW-100-B Specifications

General IconGeneral
BrandLEGRAND
ModelWattstopper DW-100-B
CategorySecurity Sensors
LanguageEnglish

Summary

Specifications

Voltages and Load Limits

Specifies operating voltages and maximum load capacities for the relays.

Load Type Compatibility

Details the types of lighting loads compatible with the sensors.

Timing and Operational Modes

Covers time delay, walk-through, and test modes for occupancy sensing.

Sensor Adjustment Parameters

Explains how to adjust the sensor's PIR, ultrasonic, and light level sensitivity.

Alerts and Patents

Describes audible alerts and lists patent information.

Description and Operation

Dual Technology Sensing

Combines PIR and ultrasonic technologies to prevent false triggering and ensure reliable detection.

Operating Modes

Details selectable modes, including walk-through and light level override functions.

Manual and Auto ON Modes

Explains how loads are turned ON manually or automatically based on occupancy.

Coverage Patterns

PIR and Ultrasonic Coverage

Describes the sensor's PIR and ultrasonic detection fields and recommended room sizes.

Masking the Lens

Instructions on using opaque tape to eliminate coverage in unwanted areas.

Installation

Wiring Instructions

Provides wiring diagrams for DW-100 and DW-200 models for different electrical setups.

Mounting and Testing

Steps for attaching the unit to the wall box and initial testing of the lights.

DIP Switch Settings and Adjustments

DIP Switch Functions

Details configurations for time delay, walk-through, PIR sensitivity, trigger mode, and alerts.

Light Level Adjustment Procedure

Guide on setting the light level threshold to control load activation based on ambient light.

Reset and Service Modes

Procedures for resetting the sensor to default settings and entering service mode.

Troubleshooting

Lights Do Not Turn ON

Diagnoses issues when lights fail to turn on, checking connections and settings.

Lights Do Not Turn OFF

Addresses problems with lights staying on, checking time delays and potential false triggers.

Sensing Motion Outside Desired Areas

Solutions for inaccurate motion detection, including sensitivity and lens masking.

Red LED Indicator Issues

Troubleshoots scenarios where the red LED is constantly lit or sensor features are non-functional.