507266-05Page 50 of 58 Issue 1933
95G2UH110CV20
Temp. Rise Speed Adjustment
Heating CFM @ 0 - 0.8” w.c.
Setting D Setting C Setting B Setting A
High Fire
45-75
+ 1560 1760 1905 1955
Normal 1415 1610 1740 1795
- 1285 1485 1560 1635
Low Fire
35-65
+ 1155 1325 1420 1500
Normal 1055 1200 1310 1360
- 935 1075 1170 1245
Cooling Stage Cooling CFM @ 0 - 0.8” w.c.
2nd Stage
+ 1310 1560 1745 1955
Normal 1220 1405 1570 1795
- 1075 1270 1430 1635
1st Stage
+ 935 1065 1245 1405
Normal 865 970 1145 1280
- 790 890 1025 1165
95G2UH135DV20
Temp. Rise Speed Adjustment
Heating CFM @ 0 - 0.8” w.c.
Setting D Setting C Setting B Setting A
High Fire
55-85
+ 1650 1845 2000 2055
Normal 1495 1660 1880 1905
- 1360 1500 1670 1705
Low Fire
40-70
+ 1300 1435 1630 1652
Normal 1190 1325 1465 1491
- 1095 1190 1340 1343
Cooling Stage Cooling CFM @ 0 - 0.8” w.c.
2nd Stage
+ 1395 1640 1840 2055
Normal 1290 1480 1660 1905
- 1170 1330 1500 1705
1st Stage
+ 1015 1160 1330 1480
Normal 940 1085 1200 1345
- 870 965 1110 1225