• 24 •
AQUALEAN - AWC/AWH - MIL118E-1407 / 10-2013
INSTALLATION
3.2.- UNIT INSTALLATION
a) Cooling mode
[Cooling capacity (kW) + Total absorbed power (kW)] x 860
t =
______________________________________________
Water ow (l/h)
a) Heating mode
[Heating capacity (kW) + Total absorbed power (kW)] x 860
t =
____________________________________________
Water ow (l/h)
If the compressor noise is ver
y
hi
g
h and in addition, hi
g
h and low pressure values are similar,
i
t can be possible a wron
g
phase electrical connection. In this case, please chan
g
e the
c
onnection for two phases.
(
Units 012 to 020
).
All the data water ow, cooling / heating capacity and power input are on the capacity tables according to each model and the working
conditions.
After a few minutes, when the unit will be stabilised, you have to verify:
- High and low pressure values and in addition saturation temperatures according to the correct working mode of the unit.
- Gas reheating values are below 12ºC.
If it is not correct, please check expansion system and refrigerant leaks.
After supply the power to the unit and connect inlet/outlet water:
- Connect the gauges in high pressure and low pressure side.
- Use a temperature probe in the compressor gas pipe and another ones in the inlet and outlet water pipes.
- Start water pump.
- Make sure to close the unit all panels have to be correctly situated.
- Start the unit and make sure that the thermostat temperature adjustment is correct.
- Check the correct water ow with a differential gauge device connected between the inlet and outlet water connections in order
to know the pressure difference. Check it according to the capacity table values.
In addition, you can know the correct water ow with Dt measurement (inlet temperature ºC - outlet temperature ºC).
This value has to be the same as the value calculated with this formula:
- Outlet and inlet water temperature are correct according to the water ow which is between speci ed values.
(Units 007 to 020).
After verify the correct working mode, please stop the unit, disconnect the gauges and temperature probes. and
clean water lter.
INSTALLATION PROCESS
The unit can be work properly until next maintenance revision.