Page 22
TABLE 11– ELECTRIC HEAT DATA (3 PHASE) – CB30M–41, CB30M–51 & CB30M–65
Blower Coil
Electric Heat kW,
Number of Volts kW
Btuh
Blower
{Minimum Circuit
Number
& Shipping Weight
Steps Input Input
Input
Amps
Ampacity
b 460v–3 ph b
440 8.4 28,700 1.1 15
10 kW
-
(28K47)
3 steps
460 9.2 31,400 1.1 16
s.
g
480 10.0 34,100 1.1 16
-
440 12.6 43,000 1.1 22
15 kW
-
(28K48)
3 steps
460 13.8 47,000 1.1 23
s.
g
480 15.0 51,200 1.1 24
440 8.4 28,700 1.3 16
10 kW
-
(28K47)
3 steps
460 9.2 31,400 1.3 16
s.
g
480 10.0 34,100 1.3 17
440 12.6 43,000 1.3 22
15 kW
-
(28K48)
3 steps
460 13.8 47,000 1.3 23
s.
g
480 15.0 51,200 1.3 24
-
440 16.8 57,300 1.3 29
20 kW
-
(28K49)
3 steps
460 18.4 62,700 1.3 29
s.
g
480 20.0 68,200 1.3 32
440 21.0 71,700 1.3 36
25 kW
-
(28K50)
3 steps
460 23.0 78,300 1.3 38
s.
g
480 25.0 85,300 1.3 39
440 8.4 28,700 1.3 16
10 kW
-
(28K47)
3 steps
460 9.2 31,400 1.3 17
s.
g
480 10.0 34,100 1.3 17
440 12.6 43,000 1.9 23
15 kW
-
(28K48)
3 steps
460 13.8 47,000 1.9 24
s.
g
480 15.0 51,200 1.9 25
-
440 16.8 57,300 1.9 30
20 kW
-
(28K49)
3 steps
460 18.4 62,700 1.9 31
s.
g
480 20.0 68,200 1.9 32
440 21.0 71,700 1.9 37
25 kW
-
(28K50)
3 steps
460 23.0 78,300 1.9 39
s.
g
480 25.0 85,300 1.9 40
b 575v–3 ph b
550 16.8 57,300
1.3
24
20 kW
-
(28K51)
3 steps
575 18.4 62,700
1.3
25
s.
g
600 20.0 68,200
1.3
26
-
550 21.0 71,700
1.3
29
25 kW
-
(28K52)
3 steps
575 23.0 78,300
1.3
31
s.
g
600 25.0 85,300
1.3
32
550 16.8 57,300
1.9
24
20 kW
-
(28K51)
3 steps
575 18.4 62,700
1.9
26
s.
g
600 20.0 68,200
1.9
26
-
550 21.0 71,700
1.9
30
25 kW
-
(28K52)
3 steps
575 23.0 78,300
1.9
31
s.
g
600 25.0 85,300
1.9
32
{Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F (75_C).
Electric heater capacity only — does not include additional blower motor heat capacity.
Minimum circuit ampacity for blower motor only.
ALL 575v ELECTRIC HEATERS ARE USED WITH 460v CB30M-51 & CB30M-65 MODEL BLOWER COIL UNITS – A 575v to 460v STEP-DOWN TRANS-
FORMER FOR THE BLOWER COIL UNIT IS FURNISHED WITH ALL 575v ELECTRIC HEATERS.
Blower motor is rated at 460v.