Page 12
The  EL195UHNE  furnace  can  be  installed  in  horizontal 
applications with either right- or left-hand air discharge. 
Refer to gure 17 for clearances in horizontal applications
.
Horizontal Application
Installation Clearances
dnE thgiRdnE tfeL
Right-Hand Discharge
Left-Hand Discharge
Top
Bottom (Floor)**
Bottom (Floor)**
dnE thgiRdnE tfeL
Air
Flow
Air
Flow
Air
Flow
Air
Flow
Top 1
Front* 1
Back 1
Ends 1
Vent 1
Floor 1‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
**An 8” service clearance must be maintained below the unit to
provide for servicing of the condensate trap.
‡For installations on a combustible floor, do not install the furnace
directly on  carpeting,  tile  or other combustible materials  other
than wood flooring.
Figure 17   
Suspended Installation of Horizontal Unit
This furnace may be installed in either an attic or a crawl-
space. Either suspend the furnace from roof rafters or 
oor joists, as shown in gure 18, or install the furnace on 
a platform, as shown in gure 19. A horizontal suspension 
kit (51W10) may be ordered from Lennox or use equiva-
lent.
NOTE - Heavy-gauge sheet metal straps may be used to 
suspend the unit from roof rafters or ceiling joists. Straps 
are used to suspend the unit in this way, support must be 
provided for both the ends. The straps must not interfere 
with  the  plenum  or  exhaust  piping  installation.  Cooling 
coils and supply and return air plenums must be sup-
ported separately.
HORIZONTAL SUSPENSION KIT
Bracket
(typical)
Metal Strap
(typical)
Air
Flow
Internal Brace
(provided with kit)
Figure 18   
NOTE - When the furnace is installed on a platform or with
 the horizontal suspension kit in a crawlspace, it must be 
elevated  enough  to  avoid  water  damage,  accommodate 
drain trap and to allow the evaporator coil to drain.
Platform Installation of Horizontal Unit
1 -   Select location for unit keeping in mind service and 
other necessary clearances. See gure 17.
2 -  Construct a raised wooden frame and cover frame 
with a plywood sheet. If unit is installed above 
nished space, fabricate an auxiliary drain pan to be 
installed under unit. Set unit in drain pan as shown 
in  gure  19.  Leave  8  inches  for  service  clearance 
below unit for condensate trap.
3 -  Provide a service platform in front of unit. When 
installing the unit in a crawl space, a proper support 
platform may be created using cement blocks.
4 -  Route auxiliary drain line so that water draining from 
this outlet will be easily noticed by the homeowner.
5  -   If necessary, run the condensate line into a condensate 
pump to meet drain line slope requirements. The 
pump must be rated for use with condensing 
furnaces. Protect the condensate discharge line 
from the pump to the outside to avoid freezing.
6 -   Continue with exhaust, condensate and intake piping 
installation according to instructions.