Furnace with Evaporator Coil Using a Separate Drain
(Unit shown in horizontal left-hand discharge position)
.
5’ max.
PVC Pipe Only
4”min
5”max
Evaporator
Coil
Drain
Pan
Condensate
DrainConnection
Field Provided Vent
(4” min. to 5” max. above
condensate connection)
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
(Trap at coil is optional)
FIGURE 51
Furnace with Evaporator
Coil Using a Common Drain
(1” min.to2 Max.above
condensate
drain connection)
Condensate
Drain
Connection
Evaporator drain
line required
(Trap at coil is optional)
FIGURE 52
IMPORTANT
      
      
         

Furnace with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Condensate Drain
Connection
(4” min.to5 Max.above
condensatedrain
connection)
5’ max.
PVC Pipe Only
4”min
5”max
Evaporator
Coil
Drain
Pan
Piping from furnace and evaporator coil must slope
down a minimum 1/4” per ft. toward trap
(Trap at coil is optional)
FIGURE 53