Page 20
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a 
venting system commonly run with separate gas applianc-
es, the venting system is likely to be too large to properly 
vent the remaining attached appliances.
Conduct the following test while each appliance is oper-
ating and the other appliances (which are not operating) 
remain connected to the common venting system. If the 
venting system has been installed improperly, you must 
correct the system as indicated in the general venting re-
quirements section.
 WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each 
appliance connected to the venting system being placed 
into operation could result in carbon monoxide poisoning 
or death.
The following steps shall be followed for each appliance 
connected to the venting system being placed into 
operation, while all other appliances connected to the 
venting system are not in operation:
1 -   Seal any unused openings in the common venting 
system.
2 -   Inspect  the  venting  system  for  proper  size  and 
horizontal pitch. Determine that there is no blockage, 
restriction, leakage, corrosion, or other deciencies 
which could cause an unsafe condition.
3 -   Close all building doors and windows and all 
doors between the space in which the appliances 
remaining connected to the common venting system 
are located and other spaces of the building. Turn 
on clothes dryers and any appliances not connected 
to the common venting system. Turn on any exhaust 
fans, such as range hoods and bathroom exhausts, 
so they will operate at maximum speed. Do not 
operate  a  summer  exhaust  fan.  Close  replace 
dampers.
4 -   Follow the lighting instructions. Turn on the appliance 
that is being inspected. Adjust the thermostat so 
that the appliance operates continuously.
5 -   After the burner have operated for 5 minutes, test for 
leaks of ue gases at the draft hood relief opening. 
Use the ame of a match or candle.
6 -   After determining that each appliance connected 
to the common venting system is venting properly, 
(step 3) return all doors, widows, exhaust fans, 
replace  dampers,  and  any  other  gas-burning 
appliances to their previous mode of operation.
7 -   If a venting problem is found during any of the 
preceding tests, the common venting system must 
be modied to correct the problem.
Resize  the  common  venting  system  to  the  minimum 
vent  pipe  size  determined  by  using  the  appropriate 
tables in Appendix G. (These are in the current stan-
dards of the National Fuel Gas Code ANSI Z223.1.