Page 30
GAS VALVE SHOWN IN ON POSITION
INLET PRESSURE POST
HIGH FIRE ADJUSTMENT
SCREW
(under cap)
MANIFOLD
PRESSURE TAP
WHITE RODGERS GAS VALVE
FIGURE 31 
8 -   Move switch on gas valve to ON. Do not force. See 
gure 31.
9 -  Replace the upper access panel.
10 -  Turn on all electrical power to to the unit.
11 - Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11 
may need to be repeated to purge air from gas line.
12 -  If the appliance will not operate, follow the 
instructions “Turning Off Gas to Unit” and call your 
service technician or gas supplier.
Turning Off Gas to Unit
1 -  Set the thermostat to the lowest setting.
2 -   Turn off all electrical power to the unit if service is to 
be performed.
3 -  Remove the upper access panel.
4 -  Move switch on gas valve to OFF. Do not force.
5 -  Replace the upper access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 -  Is the thermostat calling for heat?
2 -  Are access panels securely in place?
3 -  Is the main disconnect switch closed?
4 -  Is there a blown fuse or tripped circuit breaker?
5 -   Is the lter dirty or plugged? Dirty or plugged lters 
will cause the limit control to shut the unit off.
6 -  Is gas turned on at the meter?
7 -  Is the manual main shut-off valve open?
8 -  Is the gas valve ON/OFF switch in the ON position?
9 -   Is the unit ignition system in lock out? If the unit locks 
out again, call the service technician to inspect the 
unit for blockages.
10 -  Is  pressure  switch  closed?  Obstructed  ue  will 
cause unit to shut off at pressure switch. Check ue 
and outlet for blockages.
11 -  Are ame rollout switches  tripped?  If  ame  rollout 
switches are tripped, call the service technician for 
inspection.
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 9 
GAS METERING CLOCKING CHART
EL280 
Unit
Natural 1000 btu/cu ft LP 2500 btu cu/cu ft
Seconds For One Revolution
1 cu ft dial 2 cu fr dial 1 cu ft Dial 2 cu ft Dial
-045 80 160 200 400
-070 55 110 136 272
-090 41 82 102 204
-110 33 66 82 164
-135 27 54 68 136
Furnace should operate at least 5 minutes before check-
ing  gas  ow.  Determine  time  in  seconds  for  two  revolu-
tions of gas through the meter. (Two revolutions assures 
a more accurate time.) Divide by two and compare to time  
in table 9 below. If manifold pressure matches table 11 
and rate is incorrect, check gas orices for proper size and 
restriction. Remove temporary gas meter if installed.
NOTE - To obtain accurate reading, shut off all other gas 
appliances connected to meter.
Supply Pressure Measurement
An inlet post located on the gas valve provides access 
to the supply pressure. See gure 31. Back out the 3/32” 
hex screw one turn, connect a piece of 5/16” tubing and 
connect to a manometer to measure supply pressure. See 
table 11 for supply line pressure.
Manifold Pressure
A manifold pressure post located on the gas valve pro-
vides  access  to  the  manifold  pressure.  See  gure  31. 
Back out the 3/32 hex screw one turn, connect a piece 
of 5/16” tubing and connect to a manometer to measure 
manifold pressure.
NOTE - Pressure test adapter kit (10L34) is available from 
Lennox to facilitate manifold pressure measurement.
1 -   Connect test gauge to manifold pressure post 
(gure 31) gas valve.
2 -   Ignite unit on high re and let run for 5 minutes to 
allow for steady state conditions.
3 -   After  allowing  unit  to  stabilize  for  5  minutes,  record 
manifold pressure and compare to value given in table 
11.
4 -   If necessary, make adjustments. Figure 31 shows 
location of high re adjustment screw.
5 -   If  an  adjustment  is  made  on  high  re,  re-check 
manifold pressure on low re. Do not adjust low re 
manifold  pressure.  If  low  re  manifold  pressure  is 
more  than  1/2”  above  or  below  value  specied  in 
table 11, replace valve.
6 -   soon as an accurate reading has been obtained. 
Turn the supply and manifold 3/32” hex screw one 
revolution back into the gas valve.
7 -   Start unit and perform leak check. Seal leaks if 
found.