Page 23
7. Combustion Air Inducer (B6)
All EL280UHE(X) units use a two-stage combustion air in-
ducer to move air through the burners and heat exchanger 
during heating operation. The blower uses a 120VAC mo-
tor. The motor operates during all heating operation and 
is controlled by integrated control A92. The inducer  also 
operates for 15 seconds before burner ignition (pre-purge) 
and for 5 seconds after the gas valve closes (post-purge). 
The inducer operates on low speed during rst-stage heat, 
then switches to high speed for second stage heat.
NOTE - Each furnace model uses a unique CAI. Refer to 
Lennox Repair Parts listing for correct inducer for replace-
ment. 
A pressure switch connected to the combustion air induc-
er  orice  plate  is  used  to  prove  inducer  operation.  The 
combustion  air  inducer  orice  will  be  dierent  for  each 
model. See table 10 for orice sizes. The switch monitors 
air pressure in the inducer housing. During normal oper-
ation, the pressure in the housing is negative. If pressure 
becomes  less  negative  (signifying  an  obstruction  in  the 
ue) the proving switch opens. When the proving switch 
opens, the furnace control (A92) immediately closes the 
gas valve to prevent burner operation.
TABLE 10 
EL280UHE(X) Unit C.A.I. Orice Size (in)
-045E36A 1.063
-070E36A 1.375
-090E36B 1.625
-090E48B 1.690
-110E48C 1.875
-110E60C 1.875
8. Combustion Air Inducer pressure Switch (S18)
EL280UHE(X) series units are equipped with a dual com-
bustion  air  pressure  switch  (rst  and  second  stage)  lo-
cated on the combustion air inducer orice bracket. See 
gure 16. The switch is connected to the combustion air 
inducer  housing  by  means  of  a exible  silicone  hose.  It 
monitors  negative  air  pressure  in  the  combustion  air  in-
ducer housing.
The switches are a single-pole single-throw proving switch 
electrically connected to the  integrated  control. The pur-
pose  of  the  switch  is  to  prevent  burner  operation  if  the 
combustion air inducer is not operating or if the  ue  be-
comes obstructed.
On heat demand (rst or second stage) the switch senses 
that  the  combustion  air  inducer  is operating.  It  closes  a 
circuit to the integrated control when pressure inside the 
combustion air  inducer  decreases to  a  certain set  point. 
Set  points  vary  depending  on  unit  size.  See  table  11. 
The  pressure  sensed  by  the  switch  is  negative  relative 
to atmospheric pressure. If the ue becomes obstructed 
during  operation,  the  switch  senses  a  loss  of  negative 
pressure (pressure becomes more equal with atmospher-
ic pressure)  and  opens the  circuit  to the  furnace  control 
and gas valve. A bleed port on the switch allows relatively 
dry air in the vestibule to purge switch tubing, to prevent 
condensate build up.
COMBUSTION AIR PRESSURE SWITCH
Tap
High Fire
Switch
Low Fire
Switch
Bracket
FIGURE 16 
NOTE - The switch is factory set and is not eld adjust-
able. It is a safety shut-down control in the furnace and 
must not be by-passed for any reason. If switch is closed 
or bypassed, the control will not initiate ignition at start up.
TABLE 11 
0 - 4500 FT
EL280UHE(X) 
Unit
Set Point Low 
Heat (in w.c.)
Set Point High 
Heat (in w.c.)
-045E36A 0.30
0.68
-070E36A 0.35
-090E36B
0.30
-090E48B
-110E48C
-110E60C
NOTE - See table 15 for high altitude pressure switch kits.