Page 25
II-PLACEMENT AND INSTALLATION
Make sure unit is installed in accordance with installation 
instructions and applicable codes.
III-START-UP
A-Preliminary and Seasonal Checks
1 -   Inspect  electrical  wiring,  both  eld  and  factory 
installed for loose connections. Tighten as required.
2 -   Check  voltage  at  disconnect  switch.  Voltage  must 
be  within  range  listed  on  the  nameplate.  If  not, 
consult  the  power  company  and  have  voltage 
condition corrected before starting unit.
B-Heating Start-Up
 WARNING
Shock and burn hazard.
EL280UHE(X) units are equipped with a hot surface 
ignition system. Do not attempt to light manually.
1 -   STOP! Read the safety information at the beginning 
of this section.
2 -   Set the thermostat to the lowest setting.
3 -   Turn o all electrical power to the unit.
4 -   This  furnace  is  equipped  with  an  ignition  device 
which automatically lights the burners. Do not try to 
light the burners by hand.
5 -  Remove the access panel.
6 -   Turn switch on gas valve to OFF. Do not force. See 
gure 18.
7 -   Wait ve minutes to clear out any gas. If you then 
smell gas, STOP! Immediately call your gas supplier 
from a neighbor’s phone. Follow the gas supplier’s 
instructions. If you do not smell gas go to next step.
GAS VALVE SHOWN IN ON POSITION
INLET PRESSURE POST
HIGH FIRE ADJUSTMENT
SCREW
(under cap)
MANIFOLD
PRESSURE TAP
LOW FIRE ADJUSTMENT
SCREW
(under cap)
FIGURE 18 
8 -   Move switch on gas valve to ON. Do not force. See 
gure 18.
9 -  Replace the access panel.
10 - Turn on all electrical power to to the unit.
11 - Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11 
may need to be repeated to purge air from gas line.
Turning O Gas To Unit
1 -  Set thermostat to lowest setting.
2 -   Turn o all electrical power to unit if service is to be 
performed.
3 -   Remove access panel.
4 -   Move switch on valve to OFF. Do not force.
5 -   Replace access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 -   Is the thermostat calling for heat?
2 -   Are access panels securely in place?
3 -   Is the main disconnect switch closed?
4 -   Is there a blown fuse or tripped circuit breaker?
5 -   Is the lter dirty or plugged? Dirty or plugged lters 
willcause the limit control to shut the unit o.
6 -   Is gas turned on at the meter?
7 -  Is the manual main shut-o valve open?
8 -   Is the gas valve ON/OFF switch in the ON position?
9 -   Is the unit ignition system in lock out? If the unit locks 
out again, call the service technician to inspect the 
unit for blockages.
10 -  Is  pressure  switch  closed?  Obstructed  ue  will 
cause unit to shut o at pressure switch. Check ue 
and outlet for blockages.
11 -  Are ame  rollout  switches  tripped? If ame  rollout 
switches are tripped, call the service technician for 
inspection.
C-Safety or Emergency Shutdown
Turn o unit power. Close manual and main gas valves.
D-Extended Period Shutdown
Turn o thermostat or set to “UNOCCUPIED” mode. Close 
all gas valves (both internal and external to unit) to guar-
antee no gas leak into combustion chamber. Turn o pow-
er to unit. All access panels and covers must be in place 
and secured.
IV-HEATING SYSTEM SERVICE CHECKS
A-CSA Certication
All units are CSA design certied without modications.
Refer to the EL280UHE(X) Installation Instruction.
B-Gas Piping
 WARNING
If  a  exible  gas  connector  is  required  or  allowed 
by the authority that has jurisdiction, black iron 
pipe shall be installed at the gas valve and extend 
outside the furnace cabinet.
 WARNING
If  a  exible  gas  connector  is  required  or  allowed 
by the authority that has jurisdiction, black iron 
pipe shall be installed at the gas valve and extend 
outside the furnace cabinet.