Page 47
On Board Links
Note: In communicating systems with a conventional out-
door unit (non-communicating), the on-board clippable 
links must be set to properly congure the system.
On-Board Link W914 Dehum or Harmony (R to DS)
On-Board Link W914 Dehum or Harmony (R to DS) On-
board link  W914,  is  a clippable connection  between  ter-
minals  R  and  DS  on  the  integrated  control.  W914  must 
be cut when the furnace is installed with either  the  ZSV 
varaiable  zoning  system  control  or  a  thermostat  which 
features humidity control. If the link is left intact the PMW 
signal from the ZSV control will be blocked and also lead 
to control damage
Refer to TABLE 12 for operation sequence in applications 
including  EL296UHV,  a  thermostat  which  features  hu-
midity control and a single-speed outdoor unit. TABLE 13 
gives the operation sequence in applications with a two-
speed outdoor unit.
On-Board Link W951 Heat Pump (R to O)
On-board  link  W951  is  a  clippable  connection  between 
terminals R and O on the integrated control. W951 must 
be cut when the furnace is installed in applications which 
include a heat pump unit and a thermostat which features 
dual fuel use. If the link is left intact, terminal “O” will re-
main energized eliminating the HEAT MODE in the heat 
pump.
On-Board Link W915 2 Stage Compr (Y1 to Y2)
On-board  link  W915  is  a  clippable  connection  between 
terminals Y1 and Y2 on the integrated control. W915 must 
be cut if two-stage cooling will be used. If the Y1 to Y2 link 
is  not  cut  the  outdoor  unit  will  operate  in  second-stage 
cooling only.
TABLE 12 
OPERATING SEQUENCE 
Non-Communicating Thermostat with Humidity Control Feature and Single-Speed Outdoor Unit
OPERATING SEQUENCE SYSTEM DEMAND SYSTEM RESPONSE
System
Condition
Step
Thermostat Demand Relative Humidity
Compre 
ssor
Blower 
CFM 
(cool)
Comments
Y1 O G W1 Status D
NO CALL FOR DEHUMIDIFICATION
Normal Operation 1 On On On Acceptable
24 
VAC
High 100%
Compressor and 
indoor blower follow 
thermostat demand
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
24 
VAC
High 100%
CS7500 thermostat 
energizes Y1 and de-
energizes D on a call 
for de-humidication
Dehumidication 
call
2 On On On Demand 0 VAC High 70%
PRECISION MODE (operates independent of a Y1 demand)
Normal Operation 1 On On On Acceptable
24 
VAC
High 100%
Dehumidication 
mode begins when 
humidity is greater 
than set point
Dehumidication 
Call
2 On On On Demand 0 VAC High 70%
Dehumidication 
Call Only
1 On On On Demand 0 VAC High 70%
CS7500 thermostat 
will try to maintain 
room humidity setpoint 
by allowing the room 
space to maintain 
a cooler room 
thermostat setpoint**
Jumpers at indoor unit with a single stage outdoor unit. With Condensing unit - Cut 
W914 (R to DS) on SureLight
®
 control With Heat Pump - Cut W914 (R to DS) & 
W951 (R to O) on SureLight
®
 control
CS7000 thermostat to use for this application - Y2081 4 heat / 2 cool
*Dehumidication blower speed is 70% of COOL speed for all units .
**In Precision mode, CS7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room setting.