Page 57
TABLE 20 
7501 - 10000’
Unit Set Point Low Heat  Set Point High Heat
-045 0.35 0.50
-070-1 through -6 0.41 0.74
-070-7 & later 0.40 .070
-090 0.45 0.81
-110 0.41 0.74
-135 0.41 0.74
Pressure Switch Check
To check pressure switch dierential, refer to FIGURE 18 
and use the provided ttings and tubing to follow the steps 
below.
1 -   Remove thermostat demand and allow unit to cycle 
o.
2 -  Remove  the  tubing  from  the  negative  side  (red 
and  black  or  red)  and  positive  side  (black)  of  the 
pressure switch (leave both connected to cold end 
header box).
3 -  Take the 2” length square tubing and connect to the 
positive (+) side of the pressure switch. Take the 10” 
length  square  tubing  and  tee  into  the  tubing  from 
the  positive  side  of  the  cold  end  header  box  and 
the other side of the 2” square tubing. Connect the 
other end of the 10” square tubing the positive (+) 
side of the measuring device.
4 -  Take a second piece the 2” length square tubing and 
connect  to  the  negative  (-)  side  of  the  pressure 
switch. Take  a  second  piece  of  10”  length  square 
tubing  and  tee  into  the  tubing  from  the  negative 
(-)  side  of  the  cold  end  header  box  and  the  other 
side of the 2” square tubing. Connect the other end 
of the 10” square tubing to the negative (-) side of 
the  measuring  device.  Operate  unit  and  observe 
manometer reading. Readings will change as heat 
exchanger warms.
a.   Take one reading immediately after start-up.
b.   Take  a  second  reading  after  unit  has  reached  steady 
state  (approximately  5  minutes).  This  will  be  the  pressure 
dierential.
The  pressure  dierential  should  be  at  least  0.15” 
greater than those listed in the tables 18, 19 and 20. 
Readings in table are the set points or “break points”.
5 -  Remove thermostat demand and allow to cycle o.
6 -  Replace original pressure switch tubing.
NOTE - Pressure  dierential  values  (set  point) 
in  table  are  the  ”break”,  or  ”open”  specications. 
”Make”,  or  ”close”  pressure  dierentials  are  0.15” 
greater than the set points listed in table.
PRESSURE SWITCH CHECK
Black Tubing
(positive +)
Red and Black
or Red Tubing
(negative −)
Tee
2” long Square
Tubing
Measuring Device
10” Long Square Tubing
FIGURE 18