Page 58
4 -  Move gas valve switch to OFF.
5 -  Replace the access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 -  Is the thermostat calling for heat?
2 -   Are access panels securely in place?
3 -  Is the main disconnect switch closed?
4 -  Is there a blown fuse or tripped breaker?
5 -   Is the lter dirty or plugged? Dirty or plugged lters 
will cause the limit control to shut the unit off.
6 -  Is gas turned on at the meter?
7 -  Is the manual main shut-off valve open?
8 -  Is the internal manual shut-off valve open?
9 -   Is the unit ignition system in lockout? If the unit 
locks out again, inspect the unit for blockages.
Heating Sequence Of Operation
1 -   When thermostat calls for heat, combustion air 
inducer starts.
2 -   Combustion air pressure switch proves blower 
operation. Switch is factory set and requires no 
adjustment.
3 -   After a 15-second prepurge, the hot surface ignitor 
energizes.
4 -   After a 20-second ignitor warm-up period, the gas 
valve solenoid opens. A 4-second trial for ignition 
period begins.”
5 -   Gas is ignited, ame sensor proves the ame, and 
the combustion process continues.
6 -   If  ame  is  not  detected  after  rst  ignition  trial, 
the ignition control will repeat steps 3 and 4 four 
more times before locking out the gas valve 
(“WATCHGUARD” ame failure mode). The ignition 
control will then automatically repeat steps 1 through 
6 after 60 minutes. To interrupt the 60-minute 
“WATCHGUARD” period, move thermostat from 
“Heat” to “OFF” then back to “Heat”. Heating 
sequence then restarts at step 1.
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 19 
GAS METER CLOCKING CHART
EL296
Unit
Seconds for One Revolution
Natural LP
1 cu ft 
Dial
2 cu ft 
Dial
1 cu ft 
Dial
2 cu ft 
Dial
-045 80 160 200 400
-070 55 110 136 272
-090 41 82 102 204
-110 33 66 82 164
-135 27 54 68 136
Natural-1000 btu/cu ft LP-2500 btu/cu ft
Furnace should operate at least 5 minutes before check-
ing  gas  ow.  Determine  time  in  seconds  for  two  revolu-
tions of gas through the meter. (Two revolutions assures 
a more accurate time.) Divide by two and compare to time  
in table 20. If manifold pressure matches table 22 and rate  
is incorrect, check gas orices for proper size and restric-
tion. Remove temporary gas meter if installed.
NOTE - To obtain accurate reading, shut off all other gas 
appliances connected to meter.
Supply Pressure Measurement
An inlet post located on the gas valve provides access 
to the supply pressure. See Figure 62. Back out the 3/32 
hex screw one turn, connect a piece of 5/16 tubing and 
connect to a manometer to measure supply pressure. See 
table 22 for supply line pressure.
On multiple unit installations, each unit should be checked 
separately, with and without units operating. Supply pres-
sure must fall within range listed in table 22.
Manifold Pressure Measurement
NOTE - Pressure test adapter kit (10L34) is available from 
Lennox to facilitate manifold pressure measurement.
A manifold pressure post located on the gas valve pro-
vides access to the manifold pressure. See Figure 62. 
Back out the 3/32 hex screw one turn, connect a piece 
of 5/16 tubing and connect to a manometer to measure 
manifold pressure.
To correctly measure manifold pressure, the differential 
pressure between the positive gas manifold and the neg-
ative burner box must be considered.
1 -   Connect the test gauge positive side “+“ to manifold 
pressure tap on gas valve as noted above.
2 -   Tee into the gas valve regulator vent hose and 
connect to test gauge negative “-”.
3 -   Ignite unit  on  low  re and  let  run for  5  minutes to 
allow for steady state conditions.
4 -   After allowing unit to stabilize for 5 minutes, record 
manifold pressure and compare to value given in 
table 22.
5 -   If necessary, make adjustments. Figure 62 shows 
location of high re and low re adjustment screws.
6 -   Repeat steps 3, 4 and 5 on high re. See values in 
table 22.
7 -   Shut unit off and remove manometer as soon as 
an accurate reading has been obtained. Turn the 
supply and manifold 3/32” hex screws one revolution 
back into the gas valve.
8 -   Start unit and perform leak check. Seal leaks if 
found.