Page 32
Condensate Piping
This unit is designed for either right- or left-side exit of 
condensate  piping  in  upow  applications.  In  horizontal 
applications, the condensate trap must extend below the 
unit. An 8” service clearance is required for the conden-
sate trap. Refer to Figure 45 and Figure 47 for condensate 
trap locations. Figure 53 shows trap assembly using 1/2” 
PVC or 3/4” PVC.
NOTE - If necessary the condensate trap may be installed 
up to 5’ away from the furnace. Use PVC pipe to connect 
trap  to  furnace  condensate  outlet.  Piping  from  furnace 
must slope down a minimum of 1/4” per ft. toward trap.
1 -    Determine which side condensate piping will exit 
the unit, location of trap, eld-provided ttings and 
length of PVC pipe required to reach available 
drain.
2 -   Use  a  large  at  head  screw  driver  or  a  1/2”  drive 
socket extension and remove plug (Figure 45) from 
the cold end header box at the appropriate location 
on the side of the unit. Install provided 3/4 NPT 
street  elbow  tting  into cold end  header  box.  Use 
Teon tape or appropriate pipe dope.
NOTE - Cold end header box drain plugs are facto-
ry installed. Check the unused plug for tightness to 
prevent leakage.
3 -   Install the cap over the clean out opening at the 
base of the trap. Secure with clamp. See Figure 53.
4 -   Install  drain  trap  using  appropriate  PVC  ttings, 
glue all joints. Glue the provided drain trap as 
shown in Figure 53. Route the condensate line to 
an open drain. Condensate line must maintain a 
1/4” downward slope from the furnace to the drain.
5 -   Figure 48 and Figure 49 show the furnace and 
evaporator coil using a separate drain. If necessary 
the condensate line from the furnace and evaporator 
coil can drain together. See Figure 50, Figure 51 and 
Figure 52. Upow furnace (Figure 51) - In upow 
furnace  applications  the  eld  provided  vent  must 
be a minimum 1” to a maximum 2” length above 
the condensate drain outlet connection. Any length 
above  2”  may  result  in  a  ooded  heat  exchanger 
if the combined primary drain line were to become 
restricted.  Horizontal furnace (Figure 52) - In 
horizontal  furnace  applications  the  eld  provided 
vent must be a minimum 4” to a maximum 5” length 
above the condensate drain outlet connection. 
Any  length  above  5”  may  result  in  a  ooded  heat 
exchanger if the combined primary drain line were 
to become restricted.
CONDENSATE TRAP AND PLUG  LOCATIONS
(Unit shown in upflow position)
NOTE - In upflow applications where side return
sate trap, filter rack must be installed beyond
condensate trap or trap must be re-located to
avoid interference.
Trap
(same on
right side)
Plug
(same on left side)
1-1/2 in.
Rubber
Grommet
Figure 45 
NOTE - In  horizontal  applications  it  is  recommended  to 
install a secondary drain pan underneath the unit and trap 
assembly.
NOTE - Appropriately sized tubing and barbed tting may 
be used for condensate drain. Attach to the drain on the 
trap using a hose clamp. See Figure 46.
Field Provided Drain Components
Tubing
Hose Clamp
Barbed Fitting
Elbow
Figure 46 
 CAUTION
Do not use copper tubing or existing copper condensate 
lines for drain line.