Page 75
2  -  On  eld  supplied  terminations  for  side  wall  exit, 
exhaust piping may extend a maximum of 12 inches 
(305MM) for 2” PVC and 20 inches (508MM) for 3” 
(76MM) PVC beyond the outside wall.
3 -  If exhaust piping must be run up a side wall to position 
above  snow  accumulation  or  other  obstructions, 
piping must be supported every 24 inches (610MM). 
When  exhaust  piping  must  be  run  up  an  outside 
wall,  any  reduction  in  exhaust  pipe  size  must  be 
done after the nal elbow.
4 -  Distance  between  exhaust  pipe  terminations  on 
multiple furnaces must meet local codes.
NON-DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
UNCONDITIONED
ATTIC SPACE
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
12” (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
FIGURE 41 
NOTE - Do 
tical discharge through an existing unused chimney or stack is required, insert piping
inside 
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
INSULATE
TO FORM
SEAL
SHEET
METAL TOP
PLATE
       NON-DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
FIGURE 42 
Condensate Piping
This  unit  is  designed  for  either  right-  or  left-side  exit  of 
condensate  piping  in  upow  applications.  In  horizontal 
applications, the condensate trap must extend below the 
unit. An 8” service clearance is required for the conden-
sate trap. Refer to FIGURE 43 for condensate trap loca-
tions. FIGURE 51 (3/4” drain connection) and FIGURE 52 
(1/2”  drain  connection)  shows  trap  assembly  using  1/2” 
PVC or 3/4” PVC.
NOTE - If necessary the condensate trap may be installed 
up to 5’ away from the furnace. Use PVC pipe to connect 
trap  to  furnace  condensate  outlet.  Piping  from  furnace 
must slope down a minimum of 1/4” per ft. toward trap.
1 -   Determine  which  side  condensate  piping  will  exit 
the unit, location of trap, eld-provided ttings and 
length  of  PVC  pipe  required  to  reach  available 
drain.
2  -  For furnaces with a 1/2” drain connection use a 3/8 
allen wrench and remove plug (gure 43) from the 
cold end header box at the appropriate location on 
the  side  of  the  unit.  Install  eld-provided  1/2  NPT 
male tting into cold end header box. For furnaces 
with a  3/4”  drain connection  use  a  large  at head 
screw  driver  or  a  1/2”  drive  socket  extension  and 
remove plug. Install provided 3/4 NPT street elbow 
tting into cold end header box. Use Teon tape or 
appropriate pipe dope.
3 -  Install the cap over the clean out opening at the base 
of the trap. Secure with clamp. See FIGURE 51 or 
FIGURE 52. 
4 -  Install drain trap using appropriate PVC ttings, glue 
all joints. Glue the provided drain trap as shown in 
FIGURE 51 or FIGURE 52. Route the condensate 
line  to  an  open  drain.  Condensate  line  must 
maintain a 1/4” downward slope from the furnace to 
the drain.
CONDENSATE TRAP AND PLUG  LOCATIONS
(Unit shown in upflow position)
NOTE - In upflow applications where side return
sate trap, filter rack must be installed beyond
condensate trap or trap must be re-located to
Trap
(same on
right side)
Plug
(same on left side)
1-1/2 in.
Rubber
Grommet
FIGURE 43 
5 -     FIGURE 46 and FIGURE 48 show the furnace and 
evaporator coil using a separate drain. If necessary 
the condensate line from the furnace and evaporator 
coil can drain together. See FIGURE 47, FIGURE 
49 and FIGURE 50. Upow furnace (FIGURE 49) 
-  In  upow  furnace  applications  the  eld  provided 
vent must be a minimum 1” to a maximum 2” length 
above  the  condensate  drain  outlet  connection. 
Any  length  above  2”  may  result  in  a  ooded  heat 
exchanger if the combined primary drain line were 
to become restricted.