Page 24
7 -   Immediately  after  applying  last  coat  of  cement  to 
pipe, and while both inside socket surface and end 
of pipe are wet with cement, forcefully insert end of 
pipe into socket until it bottoms out. Turn PVC pipe 
1/4 turn during assembly (but not after pipe is fully 
inserted) to distribute cement evenly. DO NOT turn 
ABS or cellular core pipe.
NOTE - Assembly should be completed within 20 
seconds  after  last  application  of  cement.  Hammer 
blows should not be used when inserting pipe.
8 -   After  assembly,  wipe  excess  cement  from  pipe  at 
end of tting socket. A properly made joint will show 
a bead around its entire perimeter. Any gaps may 
indicate  an  improper  assembly  due  to  insucient 
solvent.
9 -   Handle joints carefully until completely set.
Venting Pratices
* See  Piping and Fittings Specifications table
Piping Suspension Guidelines
NOTE - Isolate piping at the point where it exits the outside wall or
roof in order to prevent transmission of vibration to the structure.
SCHEDULE 40
PVC - 5'
all other pipe*  - 3'
Wall
edistuoedisni
24” maximum
3/4” minimum
Wall Thickness Guidelines
FIGURE 17 
1 -   In  areas  where  piping  penetrates  joists  or  interior 
walls, hole must be large enough to allow clearance 
on all sides of pipe through center of hole using a 
hanger.
2 -   When furnace is installed in a residence where unit 
is shut down for an extended period of time, such 
as  a  vacation  home,  make  provisions  for  draining 
condensate collection trap and lines.
Removal of the Furnace from Common Vent
In  the  event  that  an  existing  furnace  is  removed  from  a 
venting system commonly run with separate gas applianc-
es, the venting system is likely to be too large to properly 
vent the remaining  attached  appliances.Conduct the fol-
lowing test while each appliance is operating and the oth-
er appliances (which are not operating) remain connected 
to the common venting system. If the venting system has 
been installed improperly, you must correct the system as 
indicated in the general venting requirements section.
 WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for 
each appliance connected to the venting system 
being placed into operation could result in carbon 
monoxide poisoning or death.
The following steps shall be followed for each 
appliance connected to the venting system being 
placed into operation, while all other appliances 
connected to the venting system are not in operation:
1 -   Seal any unused openings in the common venting 
system.
2 -   Inspect  the  venting  system  for  proper  size  and 
horizontal pitch. Determine that there is no blockage, 
restriction, leakage, corrosion, or other deciencies 
which could cause an unsafe condition.
3 -   Close  all  building  doors  and  windows  and  all 
doors between the space in  which  the  appliances 
remaining connected to the common venting system 
are located and other spaces of the building. Turn on 
clothes dryers and any appliances not connected to 
the common venting system. Turn on any exhaust 
fans, such as range hoods and bathroom exhausts, 
so  they  will  operate  at  maximum  speed.  Do  not 
operate  a  summer  exhaust  fan.  Close  replace 
dampers.
4 -   Follow the lighting instructions. Turn on the appliance 
that  is  being  inspected.  Adjust  the  thermostat  so 
that the appliance operates continuously.
5 -   After the main burner has operated for 5 minutes, 
test for  leaks of ue gases at the draft hood relief 
opening. Use the ame of a match or candle.
6 -   After  determining  that  each  appliance  connected 
to the common venting system is venting properly, 
(step  3)  return  all  doors,  widows,  exhaust  fans, 
replace  dampers,  and  any  other  gas-burning 
appliances to their previous mode of operation.