Page 24
TYPICAL AIR INTAKE PIPE CONNECTIONS
NON−DIRECT VENT APPLICATIONS
AIR
INTAKE
SCREEN
(Provided)
NOTE - Air intake  screen and elbow may be rotated, so that
screen may be positioned to face forward or to either side.
FIGURE 32 
Follow the next two steps when installing the unit in 
Non-Direct Vent applications where combustion air is tak-
en from indoors and ue gases are discharged outdoors.
1 -   Use eld-provided materials and the factory-provided 
air intake screen to route the intake piping as shown 
in FIGURE 32. Maintain a minimum clearance of 
3” (76mm) around the air intake opening. The air 
intake opening (with the protective screen) should 
always be directed forward, or sideways.
2  -   Use cement to secure the intake pipe to the connector, 
if desired.
General Guidelines for Vent Terminations
In Non-Direct Vent applications, combustion air is taken 
from indoors and the ue gases are discharged to the out-
doors. The  EL296DFV  is then  classied  as a non-direct 
vent, Category IV gas furnace.
In Direct Vent applications, combustion air is taken from 
outdoors  and  the  ue  gases  are  discharged  to  the  out-
doors. The EL296DFV is then classied as a direct vent, 
Category IV gas furnace.
In both Non-Direct Vent and Direct Vent applications, the 
vent termination is limited by local building codes. In the 
absence of local codes, refer to the current National Fuel 
Gas Code ANSI Z223-1/NFPA 54 in U.S.A., and current 
CSA-B149 Natural Gas and Propane Installation Codes in 
Canada for details.
Position termination according to location given in FIG-
URE 34 or FIGURE 35. In addition, position termination so 
it is free from any obstructions and 12” above the average 
snow accumulation.
At vent termination, care must be taken to maintain protec-
tive coatings over building materials (prolonged exposure 
to exhaust condensate can destroy protective coatings). 
It is recommended that the exhaust outlet not be located 
within 6 feet (1.8m) of an outdoor AC unit because the 
condensate can damage the painted coating.
NOTE - See TABLE 8 for maximum allowed exhaust pipe 
length  without  insulation  in  unconditioned  space  during 
winter design temperatures below 32°F (0°C). If required 
exhaust  pipe  should  be  insulated  with  1/2”  (13mm)  Ar-
maex or equivalent. In extreme cold climate areas, 3/4” 
(19mm) Armaex  or equivalent may be necessary.  Insu-
lation must be protected from deterioration. Armaex with 
UV  protection  is  permissable.  Basements  or  other  en-
closed areas that are not exposed to the outdoor ambient 
temperature and are above 32 degrees F (0°C) are to be 
considered conditioned spaces.
 IMPORTANT
Do not use screens or perforated metal in exhaust 
terminations. Doing so will cause freeze-ups and may 
block the terminations.
 IMPORTANT
For Canadian Installations Only: In accordance to CSA 
International B149 installation codes, the minimum 
allowed distance between the combustion air intake inlet 
and the exhaust outlet of other appliances shall not be 
less than 12 inches (305mm).