BLOWER DATA
EL296DF090XV60C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
+24% 1425 1895
+18% 1355 1825
+12% 1280 1740
+6% 1215 1660
Factory Default 1160 1575
–6% 1055 1455
–12% 1010 1365
–18% 950 1265
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
Low Medium-Low Medium-High
2
High Low Medium-Low Medium-High
2
High
+ 1115 1265 1400 1600 1600 1750 1970 2130
Factory Default 1005 1150 1275 1450 1450 1630 1810 1975
890 1065 1150 1270 1270 1450 1645 1810
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic
DIP Switch Settings.
2
Factory default setting.
NOTES - The e󰀨ect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28% and 38% of the selected second stage cooling speed - minimum 450 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.