TABLE 17
300 NORMAL OPERATING PRESSURES - NO REHEAT - ALL-ALUMINUM COIL - 581097-01
Outdoor Coil Entering Air Temperature
65 F 75 F 85 F 95 F 105 F 115 F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Circuit 1
112 260 113 302 115 349 117 401 119 459 121 523
120 264 122 305 124 352 126 404 128 462 131 525
137 273 140 313 142 359 145 410 147 467 150 529
155 283 158 322 161 367 164 417 167 473 171 535
Circuit 2
114 245 116 285 117 329 119 379 121 434 123 494
121 249 124 289 126 333 128 383 130 438 133 497
137 257 140 297 144 341 147 390 150 445 153 505
154 265 158 304 161 348 165 397 169 451 173 511
Circuit 3
95 259 97 300 99 346 102 398 104 454 107 515
102 264 105 306 107 352 110 403 113 459 115 520
118 274 121 315 124 362 127 413 130 469 134 530
135 282 138 323 142 370 146 421 149 478 153 539
Circuit 4
98 251 100 294 102 341 104 393 106 450 108 511
105 259 107 301 110 347 112 399 115 456 117 517
121 269 124 310 127 357 130 408 133 464 136 524
137 274 141 315 145 360 148 411 152 466 156 526
300 CHARGING CURVE CIRCUIT 1 - NO REHEAT - ALL-ALUMINUM COIL - 581098-01
Suction Pressure (psig)
70
80
90
100
110
120
Outdoor Temperature (°F)
105°
95°
115°
85°
75°
65°
60
110 120 130140 150160 170