EasyManuals Logo

Lennox Enlight LGT210H4M User Manual

Lennox Enlight LGT210H4M
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image

TABLE 11
180 NORMAL OPERATING PRESSURES - NO REHEAT - ALL-ALUMINUM COIL - 581085-01
Outdoor Coil Entering Air Temperature
65 F 75 F 85 F 95 F 105 F 115 F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Circuit 1
100 217 104 249 106 287 108 331 110 379 111 433
107 219 111 251 114 289 117 333 119 382 121 436
120 222 125 255 130 293 134 337 137 386 140 440
132 225 138 258 144 296 149 340 154 389 159 444
Circuit 2
104 243 106 283 108 327 110 375 112 428 113 485
110 246 113 286 116 330 119 378 121 431 123 489
124 251 129 292 133 336 136 385 140 439 143 496
139 258 144 299 150 344 154 393 159 447 163 505
Circuit 3
119 242 119 282 120 325 123 373 127 424 131 479
123 246 124 285 126 329 129 376 133 428 138 483
135 252 138 292 141 336 145 384 150 435 157 491
154 258 157 298 162 342 167 390 174 442 181 498
180 CHARGING CURVE CIRCUIT 1 - NO REHEAT - ALL-ALUMINUM COIL - 581086-01
Suction Pressure (psig)
70
80
90
100
110
Outdoor Temperature (°F)
105°
95°
115°
85°
75°
65°
60
061051041031021011100