ELECTRONICALLY CONTROLLED
MOTOR
ICM1
ICM2
Page 1
1998 Lennox Industries Inc.
Litho U.S.A.
Corp. 9815−L9
G21/GSR21
Service Literature
Revised 10−2001
G21/GSR21 SERIES UNITS
G21 and GSR21 units are condensing furnaces utilizing
the pulse combustion process. Initially, combustion
takes place in an enclosed chamber. Then, as combus
tion products pass through the heat exchanger system
into a coil, the latent heat of combustion is extracted and
water is condensed from the exhaust gas.
The unit uses a redundant gas valve to assure safety
shutoff as required by A.G.A. The units are manufac
tured for natural gas application. L.P. kits for A.G.A. /
C.G.A. units are available for field changeover.
An electronic direct spark ignition control initiates com
bustion. The ignition control serves four functions: pre
purge, ignition, flame sensing and postpurge. Controls
reset in the event of nuisance lockout. The control also
verifies loss of combustion during a cycle, closing the
gas valve. A differential pressure switch shuts down the
unit immediately if there are obstructions in the exhaust
outlet or air intake.
A purge blower clears the combustion chamber before and af
ter each heating cycle to ensure proper air mixture for startup.
All units feature direct drive multispeed blower motors.
V" series units feature an electronically controlled blower
motor (ICM1 or ICM2) controlled by a VSP control (VSP1 or
VSP2−1). The VSP controls blower CFM using either a
PWM (pulse width modulation) signal or fixed 24 VAC or
VDC signal.
These signals are gener
ated by optional controls
such as the Harmony zone
control system, Efficiency
Plus Humidity Control
(CCB1) or a thermostat. A
PWM signal is generated by
the Harmony zone control
system. A fixed DC signal is
generated by the Efficiency
Plus Humidity Control
(CCB1) and a 24 VAC signal
is generated by a thermo
stat.
The Harmony zone control system produces a PWM signal
to regulate blower CFM. The CCB1 varies indoor blower
speed in response to indoor humidity demand. The CCB1
produces a DC signal.
When a twospeed condensing unit is used with the Harmony
zone control system or CCB1, compressor speed as well as
indoor blower CFM are controlled more accurately than with
a conventional two stage thermostat.
All specifications in this manual are subject to change.
PULSE COMBUSTION PROCESS
EXHAUST
BACK PRESSURE IGNITION
COMBUSTION
AIR
GAS
OPEN
CLOSED
COMBUSTION
CHAMBER
TAILPIPE
SPARK
1 Gas and air enter and mix in combustion
chamber
2 − To start the cycle a spark is used to ignite the
gas and air mixture (this is one "pulse").
3 Positive pressure from combustion closes
flapper valves and forces exhaust gases down
the tailpipe.
4 Exhaust gases leaving chamber create a
negative pressure. This opens the flapper valve
drawing in gas and air.
5 At the same instant, part of the pulse is
reflected back from the tailpipe causing the
new gas and air mixture to ignite. No spark is
needed. (this is anotherpulse").
6 − Steps 4 and 5 repeat 60 to 70 times per second
forming consecutive pulses" of 1/4 to 1/2
Btuh each.
7 Latent heat is removed from combustion
products and condensate (water) is formed in
the condensate coil.
7
4
5
3
1
4
3
2
SENSOR

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Lennox G21Q3-60 and is the answer not in the manual?

Lennox G21Q3-60 Specifications

General IconGeneral
BrandLennox
ModelG21Q3-60
CategoryIndustrial Equipment
LanguageEnglish

Summary

G21 GSR21 SERIES UNITS

PULSE COMBUSTION PROCESS

Explains the step-by-step process of pulse combustion with a diagram.

ELECTROSTATIC DISCHARGE (ESD) Precautions and Procedures

SPECIFICATIONS (units equipped with conventional multi-speed blower motor)

SPECIFICATIONS (units equipped with electronically controlled blower motor)

BLOWER DATA (units equipped with conventional multi-speed blower motor)

ICM1 BLOWER PERFORMANCE

VSP1 BLOWER CONTROL BOARD (A24)

Diagnostic LED Lights

Explains the meaning of the diagnostic LED lights on the VSP1 control board for troubleshooting.

Diagnostic LED Lights

F - Ignition Control (A3)

1 - Lennox GC-1 Ignition Control (Figure 18)

3 - Johnson G891 Ignition Control (Figure 20)

4 - Ignition Control Functions For GC-1, GC-3, and G891 (Figures 21 and 22)

P - ICM1 and ICM2 BLOWER MOTOR (G21 VGSR21 V Units)

MOTOR SPEED CONTROL WITH D.C. PULSE-WIDTH MODULATION FIGURE 36

III - PROPER INSTALLATION

IV - SEASONAL MAINTENANCE

V - UNIT CHECKOUT

A - Temperature Rise

Explains how to measure and interpret the temperature rise for proper unit operation and blower speed adjustment.

B - External Static Pressure

C - Manifold Pressure

E - Flame Signal

To Measure Flame Signal-GC-1 Ignition Control:

GC-3 FLAME SIGNAL TEST FIGURE 65

H - Testing Exhaust CO2 CO Content

M - Checking Gas Input-Determine Gas Flow at Meter

VI - TROUBLESHOOTING

A - Safety Shutdown

Lists conditions that trigger a safety shutdown, such as loss of combustion or high limit cutout.

B - ICM2 Does Not Run

C - ICM1 Does Not Run

VII - TROUBLESHOOTING FLOWCHARTS

IGNITION CONTROL CHECKOUT GC1

IGNITION CONTROL CHECKOUT GC3

IGNITION CONTROL CHECKOUT G891

ELECTRICAL CHECKOUT

GAS, AIR and SPARK CHECKS

SPARK CHECKS CAUTION-HIGH VOLTAGE

Provides specific steps and safety warnings for checking the spark plug and ignition system.

ELECTRICAL TESTING

V BLOWER ICM2 MOTOR AND VSP2-1 BLOWER CONTROL BOARD TROUBLESHOOTING FLOW CHART

V BLOWER AND VSP1 BLOWER CONTROL BOARD HEATING MODE CHECKOUT

V BLOWER AND VSP1 BLOWER CONTROL BOARD COOLING MODE CHECKOUT

UNIT STARTS SPUTTER STARTS AND DIES

UNIT STARTS CLEAN BUT RUNS LESS THAN 10 SECONDS

UNIT RUNS BUT SHUTS OFF BEFORE THERMOSTAT IS SATISFIED-INSUFFICIENT HEAT

VIII-WIRING DIAGRAMS AND SEQUENCE OF OPERATION

Sequence of Operation G21 Q B-APPLICATION OF G21 Q WITH GC3 IGNITION CONTROL

TYPICAL GSR21 Q DIAGRAM (-11 MODEL SHOWN)

Sequence of Operation GSR21 Q C-APPLICATION OF GSR21 Q WITH GC3 IGNITION CONTROL

G21 V with GC3 Ignition Control WIRING DIAGRAM

D-OPERATION SEQUENCE G21 V WITH GC3 IGNITION CONTROL

Heating-Single Stage-Heating Blower jumper in position #2

Details the sequence for single-stage heating with the heating blower jumper in position #2.

G21 Q with GC3 Ignition Control WIRING DIAGRAM

Sequence of Operation G21 Q H-APPLICATION OF G21 Q WITH GC1 IGNITION CONTROL

GSR21 Q with GC3 Ignition Control WIRING DIAGRAM

Sequence of Operation GSR21 Q with GC3 Ignition Control I-APPLICATION OF GSR21 Q WITH GC3 IGNITION CONTROL

Heating-Single Stage-Heating Blower jumper in position # 2

Explains the sequence for single-stage heating with the heating blower jumper in position #2.

Sequence of Operation G21 Q J-APPLICATION OF G21 Q WITH GC1 IGNITION CONTROL

G21 V with GC1 Ignition Control WIRING DIAGRAM

Sequence of Operation G21 V With GC1 Ignition Control L-OPERATION SEQUENCE G21 V WITH GC1 IGNITION CONTROL

Sequence of Operation G21 V With GC3 Ignition Control L-OPERATION SEQUENCE G21 V WITH GC3 IGNITION CONTROL

GSR21 V with GC1 Ignition Control WIRING DIAGRAM

Sequence of Operation GSR21 V With GC1 Ignition Control M-OPERATION SEQUENCE GSR21 V WITH GC1 IGNITION CONTROL

GSR21 V with GC3 Ignition Control WIRING DIAGRAM

Sequence of Operation GSR21 V With GC3 Ignition Control N-OPERATION SEQUENCE GSR21 V WITH GC3 IGNITION CONTROL

Heating-Single Stage-NO JUMPERS

Explains the sequence for single-stage heating with no jumpers used on the GC1 control.

Cooling-Single Stage-No CCB1, No Harmony, DS Jumpered to G

Details the sequence for single-stage cooling without CCB1 or Harmony, with DS jumpered to G.

G21 VGSR21 V OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2-1 (HEATING)

G21 VGSR21 V OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2-1 (COOLING)

Single-Speed Compressor, no CCB1, no Harmony

Explains jumper settings and sequence for cooling with a single-speed compressor, no CCB1/Harmony.

G21 VGSR21 V OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2-1 (COOLING) (contd.)

G21 QGSR21 Q OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP1 OR VSP2-1 (OPTIONAL COOLING ACCESSORIES)

G21 VGSR21 V OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP1 (HEATING)

Single-Stage Heating

Explains jumper settings and sequences for single-stage heating with VSP1.

Two-Stage Heating

Details jumper settings and sequences for two-stage heating with VSP1.

Harmony Heating

Describes jumper settings and sequences for Harmony heating with VSP1.

G21 VGSR21 V OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP1 (COOLING)

G21 VGSR21 V OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP1 (COOLING) (contd.)

Related product manuals