EasyManuals Logo
Home>Lennox>Furnace>G32V Series

Lennox G32V Series User Manual

Lennox G32V Series
91 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
Page 63
B−Sequence of Operation.
Sequence depends on type thermostat used. Units are
applicable for single stage or two stage thermostats.
Both type thermostats are described below. Thermo-
stat jumper E20 dictates which mode unit will operate
in. See flow chart for more sequence detail.
SureLight Control Self Check
When there is a call for heat, the SureLight integrated con-
trol runs a self check. The control checks for S10 primary
limit, S21 secondary limit (s) and S47 rollout switch normal-
ly closed contacts. The control also checks for prove switch
S102 and low heat prove switch S128 (G32V−75 only) nor-
mally open contacts. Once self check is complete and all
safety switches are operational, heat call can continue.
Two−Stage Thermostat, Two Stage Heat. Jumper E20
set at TWO".
1− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until
S102 prove switch contacts close (switch must close
within 2 1/2 minutes or control goes into Watchguard
PROVE Switch mode.
G32V−75 ONLY − Combustion air inducer runs until
S128 prove switch contacts close (switch must close
within 2 1/2 minutes or control goes into Watchguard
PROVE Switch mode. Prove switch S102 may also
close). A 15 second pre−purge follows once S128
closes.
2− SureLight control begins 20 second ignitor warm up pe-
riod.
3− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until
flame sensed.
4− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
5− After 45 second delay, indoor blower B3 is energized
on low heat speed.
The furnace will stay in this mode until first stage de-
mand is satisfied OR a second stage heat demand is
initiated.
6− Second stage heat demand initiated. A 30 second sec-
ond stage recognition period begins.
7− The combustion air inducer ramps up to high heat
speed.
G32V−75 − S102 high heat prove switch closes.
8− Gas valve energizes second stage heat.
9− B3 indoor blower ramps up to high heat speed.
Single−Stage Thermostat, Two Stage Heat. Jumper
E20 set at SINGLE"
1− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until
S102 prove switch contacts close (switch must close
within 2 1/2 minutes or control goes into Watchguard
PROVE Switch mode.
G32V−75 ONLY − Combustion air inducer runs until
S128 prove switch contacts close (switch must close
within 2 1/2 minutes or control goes into Watchguard
PROVE Switch mode. Prove switch S102 may also
close). A 15 second pre−purge follows once S128
closes.
2− SureLight control begins 20 second ignitor warm up pe-
riod.
3− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until
flame sensed.
4− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
5− After 45 second delay, indoor blower B3 is energized
on low heat speed.
6− A 10 minute (factory set) or 15 minute (field set) second
stage heat delay period begins.
7− The combustion air inducer ramps up to high heat
speed.
G32V−75 − S102 high heat prove switch closes.
8− Gas valve energizes second stage heat.
9− B3 indoor blower ramps up to high heat speed.

Other manuals for Lennox G32V Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox G32V Series and is the answer not in the manual?

Lennox G32V Series Specifications

General IconGeneral
BrandLennox
ModelG32V Series
CategoryFurnace
LanguageEnglish

Related product manuals