GCS16(R)-411/413-50 BLOWER PERFORMANCE @ 208vGCS16(R)-411/413-50 BLOWER PERFORMANCE @ 230v
(With Downflow Supply and Return Air Openings)
(With Downflow Supply and Return Air Openings)
External Static
Pressure
(in. wg.)
Air Volume (cfm) @ Various Speeds
High
Med.
Low
0
.10
.15
.30
.40
.50
.60
High
Med.
Low
1825 1705 1540 1380
1795 1670 1510 1360
1775 1650 1495 1350
1715 1585 1440 1310
1660 1535 1390 1275
1595 1465 1325 1225
1505 1385 1235 1150
.05 1810 1690 1525 1370
.20 1755 1630 1480 1340
.25 1735 1605 1460 1325
External Static
Pressure
(in. wg.)
Air Volume (cfm) @ Various Speeds
High
Med.
Low
0
.10
.15
.30
.40
.50
.60
High
Med.
Low
1780 1545 1380 1210
1740 1515 1360 1190
1720 1500 1345 1175
1650 1445 1295 1125
1600 1400 1255 1090
1540 1350 1210 1050
1470 1285 1150 990
.05 1760 1530 1370 1200
.20 1700 1485 1330 1160
.25 1675 1465 1315 1145
NOTE - All CFM measured external to unit without accessories.
NOTE - All CFM measured external to unit without accessories.
GCS16(R)-411/413-100 BLOWER PERFORMANCE @230v
(With Horizontal Supply and Return Air Openings)
GCS16(R)-411/413-100 BLOWER PERFORMANCE @208v
(With Horizontal Supply and Return Air Openings)
GCS16(R)-411/413-100 BLOWER PERFORMANCE @ 230v
(With Downflow Supply and Return Air Openings)
GCS16(R)-411/413-100 BLOWER PERFORMANCE @ 208v
(With Downflow Supply and Return Air Openings)
External Static
Pressure
(in. wg.)
Air Volume (cfm) @ Various Speeds
High
Med.
Low
0
.10
.15
.30
.40
.50
.60
High
Med.
Low
1740 1585 1500 1370
1675 1545 1450 1330
1645 1525 1425 1310
1550 1440 1345 1240
1485 1380 1290 1190
1420 1320 1230 1135
1350 1260 1165 1075
.05 1710 1565 1475 1350
.20 1615 1490 1400 1290
.25 1580 1465 1375 1265
External Static
Pressure
(in. wg.)
Air Volume (cfm) @ Various Speeds
High
Med.
Low
0
.10
.15
.30
.40
.50
.60
High
Med.
Low
1665 1500 1370 1220
1635 1460 1330 1195
1615 1440 1310 1180
1545 1370 1240 1125
1485 1315 1190 1080
1415 1255 1135 1030
1335 1190 1080 975
.05 1650 1480 1350 1210
.20 1595 1420 1285 1165
.25 1570 1395 1265 1145
External Static
Pressure
(in. wg.)
Air Volume (cfm) @ Various Speeds
High
Med.
Low
0
.10
.15
.30
.40
.50
.60
High
Med.
Low
1700 1580 1430 1315
1635 1520 1405 1285
1600 1490 1390 1270
1505 1400 1315 1215
1430 1340 1260 1165
1370 1280 1200 1110
1300 1215 1130 1030
.05 1665 1550 1420 1300
.20 1570 1460 1370 1250
.25 1540 1430 1345 1230
External Static
Pressure
(in. wg.)
Air Volume (cfm) @ Various Speeds
High
Med.
Low
0
.10
.15
.30
.40
.50
.60
High
Med.
Low
1645 1480 1335 1175
1590 1435 1300 1150
1560 1415 1280 1135
1470 1340 1220 1090
1410 1285 1170 1055
1340 1225 1115 1020
1270 1160 1060 985
.05 1615 1455 1320 1165
.20 1530 1390 1260 1120
.25 1500 1365 1240 1105
NOTE - All CFM measured external to unit without accessories.
NOTE - All CFM measured external to unit without accessories. NOTE - All CFM measured external to unit without accessories.
NOTE - All CFM measured external to unit without accessories.
.70 1445 1345 1195 1100 .70 1400 1240 1120 945
.75 1400 1310 1160 1065 .75 1360 1215 1095 920
.70 1255 1165 1105 1015 .70 1245 1120 1020 910
.75 1220 1125 1070 980 .75 1195 1085 990 875
.70 1195 1095 995 945
.75 1160 1055 965 925
.70 1235 1150 1045 930
.75 1200 1115 1000 970
BLOWER DATA