EasyManua.ls Logo

Lennox GCS16 Series - Page 36

Lennox GCS16 Series
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 36
P-Blower/Limit Control S10/K25
Check blower control by operating unit through a heating
cycle. If blower recycles after demand is satisfied, control
should be adjusted. In any case, blower off" settings
above 90F will cause the blower to recycle frequently (af
ter a heating cycle) due to residual heat in the heat ex
change assembly. Blower off" settings above 90F may
also cause nuisance trips of secondary limit S10.
Before adjusting control, disconnect all power to unit. To
adjust the blower control, move the FAN ON" lever (figure
13) as needed so the FAN OFF" lever can be set. Con
trols in all GCS16, GCS16R and GCS16H units use a bi
metal surestart heater and the the FAN ON" lever is non
functional. Set the FAN OFF" lever to a position below
90F. Reassemble unit, reconnect power, and operate
unit through a heating cycle. If blower recycles after heat
ing demand, repeat procedure and adjust control to a low
er setting.
The limit setting is factory preset and must not be ad
justed.
VIII-INDOOR BLOWER
OPERATION / ADJUSTMENT
A-Blower Operation
NOTE - The following is a generalized procedure and
does not apply to all thermostat control systems.
1- Blower operation is dependent on the thermostat con
trol system option that has been installed in the
GCS16. Refer to the section Control System Op
tions" for detailed descriptions of blower operation.
2- Generally, blower operation is set at the thermostat
subbase fan switch. With the fan switch in the ON"
position, the blower operates continuously. With the
fan switch in the AUTO" position, the blower cycles
with demand (or, with some control systems, runs
continuously while the heating or cooling circuits
cycle).
3- In most cases, the blower and entire unit will be off
when the system switch is in the OFF" position. The
only exception is immediately after a heating demand
until blower control switches off.
B-Determining Unit CFM
1- The following measurements must be made with a dry
indoor coil. Run the blower without the cooling de
mand. Air filters must be in place when measure
ments are taken.
2- Measure static pressure external to the unit (from sup
ply to return).
To Measure Discharge Static Pressure:
a- Measure tap locations as shown in figure 36.
b- Punch a 1/4" diameter hole. Insert manometer
hose flush with the inside edge of hole or insula
tion. Seal around the hole with permagum. Con
nect the zero end of the manometer to the dis
charge (supply) side of the system. Connect the
other end of the manometer to the return duct as
above.
c- With only the blower motor running, observe the
manometer reading.
d- Seal around the hole when the check is complete.
3- The CFM can be adjusted by changing the motor
speed taps. Follow the blower speed change instruc
tions below.
FIGURE 36
STATIC PRESSURE TAP LOCATIONS
MANOMETER
UNIT
C-Blower Speed Adjustment
208v/230v ONLY
All -261, -311, -411 and -413 units (208/230V only) have
four speed leadless blower motors. The speed ports are
arranged as shown in table 17.
TABLE 17
FOUR SPEED BLOWER MOTORS
Speed Tap Number
Low
Medium-Low
Medium-High
High
Common
5
4
3
2
1
All -511, -513, -651 and -653 units (208/230V only) have
five speed leadless blower motors. The speed ports are
arranged as shown in table 18.

Related product manuals