EasyManuals Logo

Lennox GWB9-050IH-3 User Manual

Lennox GWB9-050IH-3
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
7
Table 3 - PROPANE GAS
MODEL 90-50
Stock Factory Btu Value of Propane Gas++
Settings 2300 2350 2400 2450 2500
Altitude in Ft. 0-5,000 5,000-10,000
Normal Input (MBH) 50
––
Combustion Setting (CO
2
)
10.0 -11.1% (CO < 100 ppm)
Ori ce 43331095 43331095
MODEL 90-75*
Stock Factory Btu Value of Propane Gas++
Settings 2300 2350 2400 2450 2500
Altitude in Ft. 0-5,000 5,000-10,000
Normal Input (MBH) 75
––
Combustion Setting (CO
2
)
10.0 -11.1% (CO < 100 ppm)
Ori ce 43331093
43331096*
* For model 90-75 Propane units only at altitudes above 5,000 ft., install 90-75 High Altitude Ori ce Kit #550002629 For all other
altitudes use sea level ori ce.
MODEL 90-100 **
Stock Factory Btu Value of Propane Gas++
Settings 2300 2350 2400 2450 2500
Altitude in Ft. 0-5,000 5,000-10,000
Normal Input (MBH) 100
––
Combustion Setting (CO
2
)
10.0 -11.1% (CO < 100 ppm)
Ori ce 43331091
43331091
++Contact local gas utility or distributor for Btu value of gas.
BOILERS FOR USE AT HIGH ALTITUDE - UNITED STATES INSTALLATIONS
Model 90-75 propane (LP) units only at altitudes
above 5,000 ft., install 90-75 High Altitude Ori ce Kit
#550002629*.
For all other altitudes use sea level ori ce