Page 30
TABLE 9
ELECTRIC HEAT DATA LCA072(S)(H)
Electric Heat
*Heater Only
{{Total Unit (with Power Exhaust Fan) &
Electric Heat Minimum Circuit Ampacity
Required
& Net Weight
(Required)
Steps
Input
Input
Output
1.5 hp
(1.1 kW)
2 hp
(1.5 kW)
3 hp
(2.2 kW)
1 208 7.5 25,600 39 41 44
1 220 8.4 28,700
1 230 9.2 31,400
42 44 48
EHA072-10
1 240 10.0 34,200
208/230v - 3 ph (23L68)
1 440 8.4 28,700
460v - 3 ph (27L13)
1 460 9.2 31,400
21 21 23
9 lbs. (4 kg)
575v - 3 ph (27L18)
1 480 10.0 34,200
1 550 8.4 28,700
1 575 9.2 31,400
17 18 19
1 600 10.0 34,200
1 208 11.3 38,600 51 53 57
1 220 12.6 43,000
1 230 13.8 47,100
57 59 63
EHA072-15
EHAFB-15
1 240 15.0 51,200
208/230v - 3 ph (23L69)
1 440 12.6 43,000
460v - 3 ph (27L14)
1 460 13.8 47,100
28 29 31
9 lbs. (4 kg)
EHAFB-15
1 480 15.0 51,200
1 550 12.6 43,000
1 575 13.8 47,100
23 24 25
1 600 15.0 51,200
}2 208 15.0 51,200 64 66 70
}2 220 16.8 57,400
}2 230 18.4 62,800
72 74 78
EHA072-20
EHAFB-20
}2 240 20.0 68,300
208/230v - 3 ph (23L70)
1 440 16.8 57,400
460v - 3 ph (27L15)
1 460 18.4 62,800
36 37 38
12 lbs. (6 kg)
EHAFB-15/20
1 480 20.0 68,300
1 550 16.8 57,400
1 575 18.4 62,800
29 30 31
1 600 20.0 68,300
}2 208 18.8 64,200 77 79 83
}2 220 21.0 71,700
}2 230 23.0 78,500
87 89 93
EHA072-25
EHAFB-25
}2 240 25.0 85,400
208/230v - 3 ph (23L71)
1 440 21.0 71,700
460v - 3 ph (27L16)
1 460 23.0 78,500
43 44 46
12 lbs. (6 kg)
EHAFB-20/25
1 480 25.0 85,400
1 550 21.0 71,700
1 575 23.0 78,500
35 36 37
1 600 25.0 85,400
}2 208 22.5 76,800 90 92 96
}2 220 25.2 86,100
}2 230 27.6 94,300
102 104 108
EHA072-30
EHAFB-30
}2 240 30.0 102,500
208/230v - 3 ph (23L72)
208/230v - 3 ph (27L11)
1 440 25.2 86,100
1 460 27.6 94,300
51 52 53
12 lbs. (6 kg)
575v - 3 ph (27L16)
1 480 30.0 102,500
1 550 25.2 86,100
1 575 27.6 94,300
41 42 43
1 600 30.0 102,500
NOTE — (H) indicates high efficiency units, (S) indicates standard efficiency units
{Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F (75°C).
}May be used with two stage control.
*NOTE — Heater Sub-Fuse Box is required for fusing electric heat and must be ordered extra. Factory installed heaters will have fuse box installed. Also requires LTB2 Terminal Block.