ELECTRICAL DATA 6 TON
Model No. LCA/LGA072
Line voltage data — 60 Hz
208/230v
3 phase
460v
3 phase
575v
3 phase
Full load amps 2.4 1.3 1.0
Fan Motor
Locked rotor amps 4.7 2.4 1.9
hp 1.5 2 3 1.5 2 3 1.5 2 3
Indoor
Output
kW 1.1 1.5 2.2 1.1 1.5 2.2 1.1 1.5 2.2
Full load amps 5.7 7.5 10.6 2.8 3.4 4.8 2.4 2.7 3.9
Locked rotor amps 40 46.9 66 20 20.4 26.8 15 16.2 23.4
Horsepower (W) 1/2 (363)
Optional Power
Full load amps 4.4 1.7
Locked rotor amps 4.7 4.1
Service Outlet (2) 115 volt GFCI (amp rating) 15
LCA/LGA072S MODELS
Rated load amps each 20.7 9.0 7.4
Compressor
Locked rotor amps each 156.0 70.0 54.0
With Exhaust Fan 50 60 60 25 25 25 20 20 20
size (amps)
Less Exhaust Fan 50 50 50 20 20 25 20 20 20
With Exhaust Fan 39 41 44 18 18 20 15 15 16
Circuit Ampacity
Less Exhaust Fan 34 36 39 16 16 18 13 13 15
LCA/LGA072H MODELS
Rated load amps each 19.9 9.0 7.4
Compressor
Locked rotor amps each 156.00 70.0 54.0
With Exhaust Fan 50 50 60 25 25 25 20 20 20
size (amps)
Less Exhaust Fan 50 50 50 20 20 25 20 20 20
With Exhaust Fan 38 40 43 18 18 20 15 15 16
Circuit Ampacity
Less Exhaust Fan 33 35 38 16 16 18 13 13 15
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE — Extremes of operating range are plus and minus 10 % of line voltage.
NOTE — Where current does not exceed 100 amps, HACR type circuit breaker may be used in place of fuse (U.S. only).