EasyManuals Logo

Lennox LCT048 User Manual

Lennox LCT048
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
Page 48
LGT/LCT036, 048, 060, 072
LCT072
Electric Heat Size 7.5 KW 15 KW
Unit Voltage
208/230V - 3
Ph
460V - 3Ph 575V - 3Ph
208/230V - 3
Ph
460V - 3Ph 575V - 3Ph
Power Exhaust
Option
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
Diagram Key Class
Blower
Type
Amps Amps
F3
RK or K
LS 15 15 15 15 50 50 20 20 45 45 35 35
F42
RK or K
LS - - - - - - - - 45 45 - -
F4
RK or K
1
LS 45 45 20 20 15 15 45 45 20 20 15 15
F10
2
CC
LS 8 8 8 8 8 8 8 8 8 8 8 8
F27
CC
LS - - 7.5 7.5 - - 7.5 7.5 - - - -
F30
CC
LS 5 5 - - 10 10 - - 10 10 5 5
F31
CC
HS - 15 - - - 15 - - - 15 - 15
F57
CC
HS 10 10 7.5 7.5 - - 7.5 7.5 - - 10 10
F61
2
J
HS 45 45 20 20 15 15 60 60 30 30 25 25
CB10
3
-
HS 45 45 20 20 15 15 60 60 30 30 25 25
1
When SCCR is installed, F4 fuse is Class J.
2
Fuses F10 and F61 are only used on units with SCCR installed.
3
Units using Circuit Breakers will use CB10 option.
LCT072 (Continued)
Electric Heat Size 22.5 KW 30 KW
Unit Voltage Y Volt G Volt J Volt Y Volt G Volt J Volt
Power Exhaust
Option
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
Diagram Key Class
Blower
Type
Amps Amps
F3
RK or K
LS 60 60 50 50 40 40 60 60 50 50 40 40
F42
RK or K
LS 60 60 - - - - 60 60 - - - -
F4
RK or K
1
LS 45 45 20 20 15 15 45 45 20 20 15 15
F10
2
CC
LS 8 8 8 8 8 8 8 8 8 8 8 8
F27
CC
LS - - - - 7.5 7.5 - - - - 7.5 7.5
F30
CC
LS 10 10 5 5 - - 10 10 5 5 - -
F31
CC
HS - 15 - 15 - - - 15 - 15 - -
F57
CC
HS - - 10 10 7.5 7.5 - - 10 10 7.5 7.5
F61
2
J
HS 80 80 40 40 35 30 100 100 50 50 45 40
CB10
3
J
HS 80 80 40 40 35 30 100 100 50 50 45 40
1
When SCCR is installed, F4 fuse is Class J.
2
Fuses F10 and F61 are only used on units with SCCR installed.
3
Units using Circuit Breakers will use CB10 option.