LGM SERIES
Service Literature
7.5 to 12.5 ton
38.1 to 70.3 kW
LGM092U through 1502U
The LGM, 092, 102U, 120U and 150U units are configure to
order units (CTO) with a wide selection of factory-installed
options. Units are available in 130,000 to 240,000 Btuh.
heating inputs. Gas heat sections are designed with alu
minized steel tube heat exchangers with stainless steel as
an option.
Cooling capacities range from 7.5 to 12.5 tons. Units come
standard with a fin tube condenser with two single-speed
compressors plumbed in tandem to form a single refriger
ant circuit. Units also offer mechanical cooling down to
40F.
All units are equipped with direct drive blowers. The blower
will operate at lower speeds when demand is low and in
crease to higher speeds when demand is high.
Variable speed VAV system is available as an option which
enables supply duct static measurement to control blower
CFM and discharge air temperature to control cooling
stages. All LGM units are designed to accept any of several
different energy management thermostat control systems
with minimum field wiring. Factory- or field-provided control
options connect to the unit through Smartwire connectors.
When “plugged in” the controls become an integral part of
the unit wiring.
The CORE Control System is designed to accelerate
equipment install and service. Standard with all Model L™
rooftop units, control system integrates key technologies
that lower installation costs, drive system efficiency, and
protect your investments. The CORE Unit Controller is a
microprocessor-based controller that provides flexible con
trol of all unit functions.
Information contained in this manual is intended for use by
qualified service technicians only. All specifications are
subject to change. Procedures outlined in this manual are
presented as a recommendation only and do not super
sede or replace local or state codes.
If the unit must be lifted for service, rig unit by attaching four
cables to the holes located in the unit base rail (two holes at
each corner). Refer to the installation instructions for the
proper rigging technique.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property va, personal in
jury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer
or equivalent, service agency, or the gas supplier
WARNING
To prevent serious injury or death:
1-Lock-out/tag out before performing maintenance.
2- If system power is required (e.g., smoke detector
maintenance, disable power to blower, remove fan
belt where applicable, and ensure all controllers and
thermostats are Set to the “OFF” position before per
forming maintenance.
3- Always keep hands, hair, clothing, jewelery, tools,
etc.,c away from moving parts.
CAUTION
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal in
jury. Take care while handling this equipment and
wear gloves and protective clothing.
Table of Contents
Options / Accessories Page 2.....................
Specifications Page 5............................
High Altitude Page 6.............................
Blower Data Page 7.............................
Electrical Data Page 10..........................
I-Unit Components Page 13.......................
II-Placement and Installation Page 37...............
III-Charging Page 37..............................
IV-Start Up - Operation Page 38....................
V-System Service Checks Page 40................
VI-Maintenance Page 42..........................
VII-Accessories Page 43..........................
VIII-Direct Drive Supply Air Inverter Page 49.........
XI-Wiring and Operation Sequence Page 51.........

Other manuals for Lennox LGM092U

Question and Answer IconNeed help?

Do you have a question about the Lennox LGM092U and is the answer not in the manual?

Lennox LGM092U Specifications

General IconGeneral
Product TypeAir Conditioner
Model NumberLGM092U
RefrigerantR-410A
Operating Voltage208/230V
Phase1

Summary

UNIT INFORMATION LGM SERIES

Safety Warnings and Precautions

Essential safety guidelines and warnings for unit operation and maintenance.

Unit Options and Accessories

Cooling, Heating, Blower, Cabinet, and Control Options

Details on factory-installed options for cooling, heating, blower, cabinet, and control systems.

Indoor Air Quality and Electrical Options

Options for indoor air quality enhancement and electrical configurations for the unit.

Economizer, Outdoor Air, Power Exhaust, and Other Options

Information on economizer, outdoor air, power exhaust, and other unit accessory options.

Unit Specifications

General Data and Cooling Performance

Key performance metrics including tonnage, efficiency, and cooling capacity.

Refrigerant Charge and Compressor Type

Details on refrigerant type, charge amounts, and compressor specifications.

Coil and Filter Specifications

Technical specifications for indoor/outdoor coils and filter types.

Electrical Characteristics

Electrical data including voltage, amps, and power requirements.

Gas Heat Specifications and High Altitude Derate

Gas heating input, output, efficiency, and high altitude adjustment factors.

Blower Performance Data

Static Pressure and Air Volume Requirements

Data on blower performance related to static pressure and air volume.

Power Exhaust and Accessory Air Resistance

Performance data for power exhaust and air resistance for installed accessories.

Ceiling Diffuser Air Resistance and Throw

Air resistance and air throw data for various ceiling diffuser types.

Electrical Data by Tonnage

7.5 and 8.5 Ton Electrical Data

Detailed electrical specifications for 7.5 and 8.5 ton LGM models.

10 and 12.5 Ton Electrical Data

Detailed electrical specifications for 10 and 12.5 ton LGM models.

Unit Components and Layout

Overall Parts Arrangement

Diagram illustrating the location of major components within the unit.

Control Box Parts Arrangement

Diagram showing the layout of components within the unit's control box.

Unit Components

Control Box Component Descriptions

Detailed descriptions of components found within the unit's control box.

Other Unit Component Descriptions

Descriptions of additional components like transformers, fuses, and antennas.

Sensors and Control Inputs

Temperature, Room, and CO2 Sensor Details

Information on various temperature, room, and CO2 sensors used in the unit.

Pressure, Humidity, and Economizer Sensor Details

Details on pressure, humidity, and economizer differential pressure sensors.

Refrigerant System Details

Cooling System Components

Overview of the unit's cooling system, including evaporator and condenser coils.

Compressor and Inverter Information

Details on the variable speed and fixed scroll compressors and their inverters.

Inverter Control Panel Layout

Diagram showing the arrangement of controls behind the hinged panel.

Inverter System Diagnostics and Components

Inverter Related Alarms

Table and explanation of common alarms related to the compressor inverter.

Inverter System Components

Descriptions of key components within the inverter system, like filters and transformers.

Crankcase Heaters and High Pressure Switches

Information on crankcase heaters and high pressure switches for compressor protection.

Refrigerant Circuit Components

Filter Drier, Low Pressure Switches, and Condenser Fans

Details on filter driers, low pressure switches, and condenser fan motors.

Temperature Sensors and Related Components

Information on temperature sensors and their related functions.

Evaporator Coil Thermistor Locations

Diagram showing the location of thermistors on the evaporator coil.

Condenser Coil Thermistor Locations

Diagram showing the location of thermistors on the condenser coil.

Condenser Coil Thermistor Locations (RT48 & 49)

Specific diagram for RT48 and RT49 thermistor locations on condenser coils.

Blower System Operation and Access

Blower Operation Modes

Explanation of how the blower operates in different modes based on thermostat settings.

Blower Access Procedures

Step-by-step instructions for accessing the blower assembly for servicing.

Static Pressure Readings and Blower Assembly

Guidelines for static pressure readings and accessing the direct drive blower assembly.

Direct Drive Start-Up and Configuration

Direct Drive Start-Up Procedures

Steps for initiating the direct drive blower start-up and calibration process.

Blower CFM Parameter Settings

Table detailing factory and field settings for blower CFM parameters.

Blower Motor Troubleshooting Guide

Troubleshooting guide for common issues related to the direct drive blower motor.

Component Part Numbers

Drive Component Manufacturer Numbers

Table listing manufacturer and OEM part numbers for drive components.

Gas Heat Components and Operation

Heating Section Components and Ignition Control

Overview of heating section parts and the burner ignition control system.

Ignition Sequence Timing Diagrams

Diagrams illustrating normal and retrial ignition sequences and timings.

Heat Exchanger and Burner Assembly Details

Information on the heat exchanger assembly and burner configuration.

Burner Orifice and High Temperature Limits

Details on burner orifices, their installation, and high temperature limit switches.

Flame Roll-out Limit, Air Prove Switch, Inducer, and Gas Valves

Information on safety limits, air prove switches, inducer motors, and gas valves.

Spark Electrodes and Flame Sensors

Descriptions and diagrams for spark electrodes and flame sensors.

Installation and Charging Procedures

Unit Placement and Installation Guidelines

Instructions for proper unit installation, including mounting and codes.

Refrigerant Charging Procedures

Step-by-step guide for charging the refrigerant system.

Refrigerant Charge Verification Tables

Tables providing target operating pressures for refrigerant charge verification.

Start-Up and Operation Procedures

Preliminary Checks and Cooling Start-Up

Initial checks and procedures for starting the unit in cooling mode.

Heating Start-Up and Safety Shutdown

Procedures for initiating heating start-up and emergency shutdown protocols.

System Service Checks

Heating System Gas Piping and Pressure Checks

Procedures for checking gas piping, supply pressure, and manifold pressure.

Gas Flow, Burner, Electrode, and Flame Checks

Checks for proper gas flow, burner operation, spark electrode gap, and flame sensing.

Maintenance Procedures

Cooling System Service Checks and Filter Maintenance

Procedures for cooling system checks and routine filter maintenance.

Lubrication, Blower Wheel, Coil, and Electrical Maintenance

Guidance on lubrication, blower wheel cleaning, coil maintenance, and electrical checks.

Optional Accessories

Mounting Frames, LP/Propane Kits, and Filter Switch

Information on mounting frames, LP/propane conversion kits, and dirty filter switches.

Transitions, Outdoor Air Dampers, and Diffusers

Details on duct transitions, outdoor air dampers, and supply/return diffusers.

Outdoor Air Damper Configurations

Diagrams illustrating motorized and manual outdoor air damper installations.

Economizer System

Economizer Overview and Free Cooling Modes

Explanation of the economizer system and its free cooling modes.

Exhaust Dampers and Power Exhaust Fans

Information on gravity exhaust dampers and power exhaust fan applications.

Unit Options and Controls

Cold Weather Kit, Control Systems, and IAQ/Overflow Switches

Details on cold weather kits, control systems, IAQ, and overflow switches.

Smoke Detectors and Hot Gas Reheat

Information on smoke detectors and the hot gas reheat option.

Hot Gas Reheat Refrigerant Routing

Diagrams showing the refrigerant flow for hot gas reheat operation.

Reheat and Supply Air Inverter Operation

Reheat Coil Operation and Setpoints

Explanation of reheat coil operation, setpoints, and check-out procedures.

Direct Drive Supply Air Inverter Setup

Steps for setting up the direct drive supply air inverter and blower speeds.

Supply Air Inverter Minimum CFM Settings

Table detailing minimum and maximum CFM settings for various operating modes.

Wiring Diagrams and Sequence of Operation

Gas Heat Wiring Diagrams (Y/G and J Voltage)

Wiring diagrams for gas heat operation across different voltage configurations.

Gas Heat Sequence of Operation

Detailed sequence of operation for gas heat stages and related components.

Thermostat Wiring Diagram and Notes

Wiring diagram for electronic/electromechanical thermostats and associated notes.

Economizer Wiring Diagram and Operation

Wiring diagram and operational overview of the economizer system.

Unit Sequence of Operation

Step-by-step sequence of operation for cooling and economizer modes.

Direct Drive Blower Operation and Troubleshooting

Sequence of operation and troubleshooting guide for the direct drive blower motor.