SPECIFICATIONS GAS HEAT
Heat Input Type Standard Medium High
Number of Gas Heat Stages 2 2 2


  84,500 117,000 156,000
 130,000 180,000 240,000
  104,000 144,000 192,000
 15 - 45 30 - 60 40 - 70
 2150 2250 2600
󰀩 80% 80% 80%
   
 
  
 
HIGH ALTITUDE DERATE




Gas Heat
Type
Altitude
Feet
Gas Manifold Pressure
in. w.g.
Input Rate - Btuh
(Natural Gas or LPG/Propane)
Natural Gas LPG/Propane Gas First Stage Second Stage
 2001-4500   84,500 124,000
 2001-4500   117,000 172,000
 2001-4500   156,000 230,000