Page 15
ELECTRICAL DATA 25 TON
Model No. LGM300U4
1
 Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph
Compressor 1 Rated Load Amps   7.1
Locked Rotor Amps 21 11 12
Compressor 2 Rated Load Amps  8.2 
Locked Rotor Amps   55.3
Compressor 3 Rated Load Amps 22.4  7.7
Locked Rotor Amps  75 54
Compressor 4 Rated Load Amps 22.4  7.7
Locked Rotor Amps  75 54
Outdoor Fan 
Full Load Amps
(total)
2.8 
1.4 
(8.4)
1.1 
Power Exhaust 
(2) 0.33 HP
Full Load Amps
(total)
2.4 
(4.8)
1.3 
1 
(2)
Service Outlet 115V GFI (amps) 15 15 20
Indoor Blower 
Motor
Horsepower 5 7.5 10 5 7.5 10 5 7.5 10
Full Load Amps  24.2 30.8  11 14   11
2
   Maximum 
Overcurrent 
Protection (MOCP)
Unit Only 125 150 150  70 70 50 50 
With (2) 0.33 HP 
Power Exhaust
150 150 150 70 70 80 50 50 
3
   Minimum 
Circuit 
Ampacity (MCA)
Unit Only 121  137 57   44 47 50
With (2) 0.33 HP 
Power Exhaust
 134 142      52
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
 Extremes of operating range are plus and minus 10% of line voltage.
2
 HACR type breaker or fuse.
3
 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.