E1DAMP20 MOTORIZED OUTDOOR AIR DAMPER
C1DAMP10 MANUAL OUTDOOR AIR DAMPER
FILTER BRACKET SIDE VIEW
HOOD TOP
FILTER
HOOD TOP SEAL
FIGURE 30 
      
LGM units. Refer to manufacturer’s instructions included 
with transition for detailed installation procedures.
E-E1ECON15C-2 Standard and E1ECON17C-1
High Performance Economizer (Field or Factory 
horizontal air discharge applications. The economizer 
uses outdoor air for free cooling when temperature and/
or humidity is suitable. An economizer hood is furnished 
with the economizer.
NOTE - Gravity exhaust dampers are required with power 
exhaust.
The economizer is controlled by the A55 Unit Controller. 
The economizer will operate in one of four modes. Each 
The following is a brief description. See economizer instal-
lation instruction for more detail.
In the “TMP” mode, the IMC uses input from the factory 
and RT17 Outdoor Air Sensor to determine suitability of 
outside air and economizer damper operation. When out-
door sensible temperature is less than return air sensible 
temperature, outdoor air is used for cooling. This may be 
supplemented by mechanical cooling to meet comfort de-
mands. This application does not require additional op-
tional sensors.
-
vided and -installed Honeywell C7400 enthalpy sensor 
      
and humidity (enthalpy). When outdoor air enthalpy is be-
low the enthalpy control setpoint, the economizer modu-
lates to allow outdoor air for free cooling.
       
     
opening and the other sensor is installed in the return air 
opening. When the outdoor air enthalpy is below the re-
turn air enthalpy, the economizer opens to bring in outdoor 
air for free cooling.
Global Mode - The “GLO” or global mode is used with an 
energy management system which includes a global con-
trol feature. Global control is used when multiple units (in 
one location) respond to a single outdoor air sensor. Each 
-
door sensor which is installed and wired by the controls 
contractor. Motorized Outdoor Air Damper - The “GLO” 
mode is also used when a motorized outdoor air damper 
is installed in the system.
Motorized Outdoor Air Damper - The “GLO” mode is also 
used when a motorized outdoor air damper is installed in 
the system.