TABLE 23
REHEAT OPERATION
Thermostat Mode With 24V Humidistat
Humidity Demands Operation

Compressor 1 reheat on
Compressor 1 operates at 100%
Reheat valve is energized
󰀨
Blower and outdoor fans modulate to maintain in-
door coil and discharge air temperatures

Five Minutes
Compressor 1 & 2 reheat on
Compressor 1 operates at 100%
Reheat valves are energized
󰀨
Blower and outdoor fans modulate to maintain in-
door coil and discharge air temperatures
Thermostat Mode with Zone Relative Humidity (RH) Sensor
Zone humidity is greater than Setpoint +2%
Compressor 1 reheat on
Compressor 1 modulates to maintain zone RH
Reheat valve is energized
󰀨
Blower and outdoor fans modulate to maintain in-
door coil and discharge air temperatures
Zone humidity is greater than Setpoint +2%
OR
Zone humidity is greater than Setpoint for 5 minutes
Compressor 1 & 2 reheat on
Compressor 1 modulates to maintain zone RH
Reheat valves are energized
󰀨
Blower and outdoor fans modulate to maintain in-
door coil and discharge air temperatures