Why is my Lennox LZP-4 Control Panel condensing unit receiving a signal but not turning on?
- JjuanwarnerSep 12, 2025
If the condensing unit receives a signal but does not turn on, it could be due to several reasons. The pressure switch may be open, the compressor might be off due to an internal overload protector, or the condenser control board's anti-short cycle timer might not have expired yet. Most anti-short cycle timers are 5 minutes or less. If the unit doesn't start after 5 minutes, consult the condensing unit manual for possible causes.