EasyManuals Logo

Lennox MCC Series Installation, Operating And Maintenance

Lennox MCC Series
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
Installation - Operation - Maintenance manual (IOM) AIR COOLED CHILLERS & SPLIT UNITS - 1106-E • 38 •
8.1 LIST OF THE MOST COMMON PROBLEMS – CONTINUED
PROBLEMS – SYMPTOMS
PROBABLE CAUSE
RECOMMENDED ACTION
J) THE COMPRESSOR IS NOISY
- If starting on a single winding on
compressors fitted with part winding
start or wye-delta
- Check operation of the starter
contacts, the start up time delay and
the condition of the windings
- Compressor knocking
- Broken mechanical parts inside
compressor
- Replace the compressor
a) Liquid slugging
a) Check superheat and that the
expansion valve bulb is correctly
installed
b) Expansion valve blocked in open
position
b) Repair or replace
- Suction line is unusually cold
- Broken suction valves - Replace broken valves
- High discharge pressure. The water
regulating valve or the pressure
operated water valve taps or knocks
- Pressure operated water valve
fouled, water pressure is to high or
irregular
- Clean the valve. Install and
expansion tank upstream of the
valve
- Compressor shuts down through
action of the oil pressure safety
switch
- Low oil charge - Add oil
K) DISCHARGE PRESSURE TOO HIGH
- Water is far too hot at condenser
outlet
- Water flow to low or water
temperature too high in the
condenser
- Adjust the pressure operated water
valve or the thermostat on the
cooling tower
- Water is far too cold at the
condenser outlet
- Condenser tubes fouled - Clean the tubes
- Condenser abnormally hot
- Presence of air or incondensibles in
the circuit, or excessive refrigerant
charge
- Purge incondensibles and/or air,
and recover excess refrigerant
- Chilled water leaving temperature
too high
- Excessive cooling load
- Reduce load, reduce water flow if
necessary
L) DISCHARGE PRESSURE IS TOO LOW
- Water is very cold at condenser
outlet
- Condenser water flow too high or
water temperature is too low
- Adjust the pressure operated water
valve or the thermostat on the
cooling tower
- Bubbles in sightglass - Low refrigerant charge - Repair the leak and add refrigerant

Other manuals for Lennox MCC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MCC Series and is the answer not in the manual?

Lennox MCC Series Specifications

General IconGeneral
BrandLennox
ModelMCC Series
CategoryChiller
LanguageEnglish

Related product manuals