EasyManuals Logo
Home>Lennox>Chiller>MCC Series

Lennox MCC Series User Manual

Lennox MCC Series
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
Installation - Operation - Maintenance manual (IOM) AIR COOLED CHILLERS & SPLIT UNITS - 0105-E • 19 •
tightened in the various wells, if necessary add heat conducting paste to improve contact. Make sure all sensors
are correctly fitted and that all capillary tubes are fastened.
The technical data printed at the top of the wiring diagram should correspond with those indicated on the unit
nameplate.
3) Make sure that the power supplied to the unit corresponds to its operating voltage and that phase rotation
corresponds to the direction of rotation of the compressors (screw & scroll).
4) Make sure that the water circuits mentioned in 1 are completely filled with water or brine as the case may be;
with the air bled out of all high points, including the evaporator ensuring they are perfectly clean and leaktight.
In the case of machines with water cooled condensers, the condenser water circuit must be ready to operate,
filled with water, pressure tested, bled, filter cleaned after 2 hours of operation of the water pump. Cooling tower
in operating condition, water supply and overflow checked, fan in operating condition.
5) Reset all manually resetting safety devices (where necessary).
Open power circuits to all components: compressors, fans....
6) Power up the unit with the main disconnect switch (option). Visually check the oil level in the compressor
crankcases (bullseyes). This level may vary from one compressor to another, but should never be higher than
the first third of the way up the bullseyes.
CAUTION : Power up the compressor crankcase heaters at least 24 hours before starting the unit. This will
enable the refrigerant in the crankcases to evaporate off, and prevents damage to compressors through lack
of lubrication during start up.
7) Start the pump(s) check the flow of liquid to be cooled through the heat exchangers: note the inlet and outlet
water pressures, and, using the pressure drop curves, calculate liquid flow by applying the following formula:
actual flow
1/21 PPxQQ =
where
P2 = pressure drop measured on site
P1 = pressure drop published by LENNOX for a liquid flow of Q1
Q1 = nominal flow
Q = real flow
8) On units with air cooled condensers, check for correct operation of the fans and that the protective grilles are
in good condition. Make sure that rotation is in the right direction.
9) On units with ducted fan, check the air flow and duct pressure drop.
On delivery, the drive belts are new and correctly tensioned. After the first 50 operating hours check and adjust
the tension. 80% of the total elongation of belts is generally produced during the first 15 hours of operation.
Before adjusting the tension, make sure that the pulleys are correctly aligned.
To tension the belt, set the height of motor support plate by moving the plate adjustment screws.
The recommended deflection is 16 mm per metre from centre to centre.
Check that according to the diagram below (figure 14), the following ratio remains the same.
A(mm)
20
P(mm)
The belts should always be replaced when :
- the disk is set to maximum,
- the belt rubber is worn or the wire is visible.
Replacement belts must have the same rated size as the ones they are replacing. If a
transmission system has several belts, they must all be from the same manufacturing batch
(compare serial numbers).
AP
PRELIMINARY CHECKS

Other manuals for Lennox MCC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MCC Series and is the answer not in the manual?

Lennox MCC Series Specifications

General IconGeneral
BrandLennox
ModelMCC Series
CategoryChiller
LanguageEnglish

Related product manuals