EasyManua.ls Logo

Lennox MWMA009S4-*L - Error Code: F6

Lennox MWMA009S4-*L
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
142
Error Code: F6
Description: IndoorUnitEvaporatorOutletCoilTemperatureSensorFaulty
General Note: Ifthevoltageislowerthan0.06Vorhigherthan4.94V,theLEDwilldisplaytheerror.
Temperaturesensorerror
Checktheconnectionsbetweentempera-
turesensorandPCB.Aretheconnec-
tionsgood?
Yes
No
No
Correcttheconnections
Checktheresistancevalueofthesensor
via Appendix 1 and Appendix 2.
Yes
Replaceindoororout-
doorPCB.
Isitnormal?
No
Replacethesensor.

Table of Contents

Other manuals for Lennox MWMA009S4-*L

Related product manuals