Page 28 - IOM / ROOF-TOP FLEXY Series
GAS BURNERGAS BURNER
GAS BURNERGAS BURNER
GAS BURNER
PRESSURE REDUCING VALVE SETTING
- Connect the tube of the manometer to the power
pressure inlet of a solenoid valve (5-figure 24) after
loosening the screw.
- Remove the safety plug of the expansion valve setting.
- Use a screwdriver to pre-set by placing the screw at a
depth of 34 mm.
- Place the burner(s) in operation at maximum power and
set the output pressure. Turn (clockwise) to increase the
pressure and (anticlockwise) to reduce it.
- When the pressure has been set, replace the safety
plug.
- Disconnect the pressure gauge and retighten the screw.
PRESSURE REGULATOR CONTROL OR
SETTING
This is located on the burner tiers (1 figure 24) of the gas
control assembly.
- Increase the value of set point 1 (temperature set point)
to a temperature higher than room temperature )
(variable 1).
- Wait until the operation of the burner(s) reaches maxi-
mum power.
- Connect the tube of the manometer to the injection
pressure inlet after having loosened the screw (4-figure
24).
- Wait until a stable pressure is displayed on the pressure
gauge.
- Use a 8 mm key to adjust the maximum pressure (3
figure 24) clockwise to increase it and anticlockwise to
reduce it. The maximum pressure must always be set
before setting the minimum pressure.
- The minimum pressure must be measured if the
regulator is not supplied. By disconnecting the tracer
wire 116 on card EF45 or EF46 for the one-ramp module
or the upper ramp of the two-ramp module. It can be
adjusted with a 3.5 mm screwdriver on the screw
located inside the maximum pressure setting.
- For the setting of the second ramp, disconnect the
tracer wire 116 or 126 in order to switch to low speed.
Figure 23
1
2
3
4 5
Pressure taps :
(4) : Injection
(5) : Supply
Figure 24
- Manipulate the regulator several times by connecting
and disconnecting wire 116 or 126 in order to check the
low and high speed settings.
Note : The maximum pressure setting affects the
minimum pressure setting and may have to be changed.
- When the settings are correct, connect wires 116 and
126, making sure they are properly tightened, remove
the pressure gauge and replace the safety cap.
- Restart the unit and watch the burner complete several
full cycles to ensure that all the components are working
properly.
NOTE : The minimum and maximum pressure settings
corresponding to the various gas types are listed in the table
at the end of this manual.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox ROOFTOP FLEXY FCA Series and is the answer not in the manual?

Lennox ROOFTOP FLEXY FCA Series Specifications

General IconGeneral
BrandLennox
ModelROOFTOP FLEXY FCA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals