PLANNED MAINTENANCE
REFRIGERATION CIRCUITS
At least once a year, carry out an in-depth inspection of the
refrigerant circuits.
In addition, before each season (or every 3 months if used
permanently) the tasks listed in the maintenance contract must
be performed, i.e. check the refrigerant charge, evaporation
and condensing temperatures etc...
This work must be carried out by a trained refrigeration
engineer. We shall therefore keep the details of the work and
the type of checks to be performed to a minimum.
IN ACCORDANCE WITH THE LAW
REFRIGERATION FLUIDS MUST BE COLLECTED.
DEGASSING INTO THE ATMOSPHERE IS
FORBIDDEN.
REFRIGERANT CHARGES valid for R407c and R22
Gamme FC/FH/FG/FD Gamme FX
Size Nbr of circuits kg Size Nbr of circuits kg
50 1925 22 x 4
60 27 + 730 22 x 4
70 2 8,5 + 8,5 35 22 x 5
85 2 13 + 13 40 22 x 6
100 2 13 + 13 55 22 x 6
120 2 + 1 ( 8 + 7,5 ) + 11 70 2 2 x 10
140 2 + 1 (9 + 9) + 11 85 2 2 x 11
160 4 4 x 11 100 2 2 x 12
190 4 4 x 11 110 44 x 7
140 4 4 x 7,5
170 4 4 x 8,5