Page 44
Switches 14 through 19 -- Heating Mode Blower Speed 
These switches are factory set at the OFF position which 
provides 100 % of normal speed during HIGH HEAT de-
mand, 70% of normal speed during MID-RANGE HEAT 
demand and 35% of normal speed during LOW HEAT 
demand. Switches 14, 15 and 16 are used to adjust the 
LOW HEAT blower motor speed. Switches 17, 18 and 19 
are used to adjust the HIGH HEAT blower motor speed. 
TABLE 22 provides the heating mode blower speeds that 
will  result  from  dierent  switch  settings.  Refer  to  tables 
beginning on page 42 for corresponding cfm values. See 
TABLE 24 on page 48 for allowable heating speeds.
TABLE 22 
Low Heat Blower Speeds
Thermostat 
Demand
Blower 
Speed 
Adjustments
DIP Switch Settings
Low Heat 
(R to W1)
14 15 16
+ 15% On O On
+ 7.5% On O O
Normal O O O
- 7.5% On On O
- 15% On On On
TABLE 23 
High Heat Blower Speeds
Thermostat 
Demand
Blower Speed 
Adjustments
DIP Switch Settings
High Heat 
(R to W1 & 
W2)
17 18 19
+ 15% On O On
+ 7.5% On O O
Normal O O O
- 7.5% On On O
- 15% On On On
On-Board Links
On-Board links must be clipped (when applicable) before unit 
is placed into operation with a non-communicating thermostat.
On-Board Link W914 DS to R (FIGURE 55)
On-board link W914, is a clippable connection between 
terminals DS and R on the integrated control. W914 must 
be cut when the furnace is installed with either the Harmo-
ny III  zone control or a thermostat which features humidity 
control. If the link is left intact the PMW signal from the 
Harmony III control will be blocked and also lead to con-
trol damage. See TABLE 26 on page 48 for operation 
sequence in applications including SLP99UHV, a thermo-
stat which features humidity control and a single-speed 
outdoor unit. TABLE 27  gives the operation sequence in 
applications with a two-speed outdoor unit.
On-Board Link W951 R to O (FIGURE 55)
On-board link W951 is a clippable connection between 
terminals R and O on the integrated control. W951 must 
be cut when the furnace is installed in applications which 
include a heat pump unit and a thermostat which features 
dual fuel use. If the link is left intact, terminal “O” will re-
main energized eliminating the HEAT MODE in the heat 
pump.
On-Board Link W915 Y1 to Y2 (FIGURE 55)
On-board link W915 is a clippable connection between 
terminals Y1 and Y2 on the integrated control. W915 must 
be cut if two-stage cooling will be used. If the link is not cut 
the outdoor unit will operate in second-stage cooling only.
Diagnostic LED (FIGURE 55)
The seven-segment diagnostic LED displays operating 
status,  target  airow,  error  codes  and other  information. 
The table beginning on Page 56 lists diagnostic LED 
codes.
Diagnostic Push Button (FIGURE 55)
The diagnostic push button is located adjacent to the 
seven-segment diagnostic LED. This button is used to 
enable the Error Code Recall mode and the Field Test 
mode. Press the button and hold it to cycle through a 
menu of options. Every ve seconds a new menu item will 
be displayed. When the button is released, the displayed 
item will be selected. Once all items in the menu have 
been displayed, the menu resumes from the beginning 
until the button is released.
Error Code Recall Mode
Select ”E” from the menu to access the most recent 10 
error codes. Select “c” from the Error Code Recall menu 
to clear all error codes. Button must be pressed a second 
time  while  “c”  is  ashing  to  conrm  command  to  delete 
codes. Press the button until a solid “≡” is displayed to exit 
the Error Code Recall mode.
Field Test Mode
Use the diagnostic push button to scroll through the menu 
as described above. Release the button when the LED 
ashes “-” to select the Field Test mode.
While in the Field Test mode the technician can:
•    Initiate furnace ignition and move to and hold low-re 
rate by applying a R to W1 jumper.
•    Initiate furnace ignition sequence and move to and hold 
high-re rate by applying a jumper from R to W1 and 
W2.
•    Initiate furnace ignition sequence and move to and hold 
mid-re rate by applying a jumper to R and W2.
•   Apply then remove the jumper from R to W1 and W2 to 
change the ring rate from low re to mid re and high 
re.
•    A vent calibration sequence can be initiated even if a 
thermostat signal is not present. Press and hold the 
push button until a solid “C” is displayed. Release the 
button and calibration will begin. The furnace will per-
form the high-re and low-re pressure switch calibra-
tions and display “CAL”. After calibration, the LED will 
return to the ashing “-” display.
During Field Test mode operation, all safety switches are 
still in the circuit (they are not by-passed) and indoor blow-
er  performance and timings will match DIP switch selec-
tions. Current furnace ring rate, indoor blower CFM and 
ame signal will be displayed. To exit the Field Test mode, 
press and hold the button. The menu will resume from the 
beginning. Also, cycle the main power to exit the Field Test 
mode. The integrated control will automatically exit the 
Field Test mode after 45 minutes of operation.